6
2.6.2 DIP SWITCH 2
60/50 Hz - Dip2 - switch 1: Set this switch to ON for a 60Hz
•
system. This setting is only used if the communications fail.
Normally it will be overridden by the target frequency setting in
the G/H panel. The Generator and Utility must be within 1Hz of
this nominal frequency for an inphase transfer to take place.
2.6.3 SWITCHES 2 TO 6
These switches no longer have any function.
2.6.4 SWITCHES 7 AND 8
These switches select the communications baud rate, they are for
future development and should currently both be set to off (4800
baud).
Baud Rate
Dip 8 7
4800
0
0
9600
0
1
38400
1 0 (V1.8)
57600
1 1 (V1.8)
2.6.5 SYNCHRONIZATION LIMITS
Synch requirements are:
Generator frequency within 1Hz of nominal
•
Voltage within User Programmed limits
•
Absolute Voltage difference /- 6V
•
Generator/Utility Frequency difference 0.2/- 0.0 Hz
•
Phase difference within - 7 / +0 degrees
•
(i.e. Generator voltage is earlier than Utility and catching up, this
gives some compensation for the transfer switch closing delay).
2.6.6 VOLTAGE LIMITS
Determination of good Utility is done by the H or G controller
against user programmable limits. If the communication link to the
transfer switch breaks down, the following criteria are used for a
local determination.
Dropout — any phase outside - 70 to +130 % of nominal (not
the average voltage)
Pickup — all phases > +75 % of nominal
2.7 PROGRAMMING
The HTS transfer switch is controlled by the G/H control panel on
the engine generator. The timer, voltage pickup, dropout and exer-
cise settings are programmed into the G/H control panel. Please
refer to the G/H control panel manual for details on programming
the HTS transfer switch controls.
2.8 AUXILIARY
CONTACTS
It is possible to add Auxiliary Contacts on the transfer switch to
operate customer accessories, remote advisory lights, or remote
annunciator devices. It is necessary to change the single pole limit
switch to a double pole device. Reconnect 0A, 147 and 148 to like
terminals on the double limit switch. A suitable power source must
be connected to the COMMON (C) terminal (Figure 2.3).
Contact operation is shown in the following chart:
Switch Position
Utility
Standby
Common to Normally Open
Closed
Open
Common to Normally Closed
Open
Closed
NOTE:
Auxiliary Contacts are rated 10 amps at 125 or 250 volts AC.
DO NOT EXCEED THE RATED VOLTAGE AND CURRENT OF THE
CONTACTS.
Figure 2.3 — Auxiliary Contact Diagram
Section 2 — Installation
HTS “Wn” Type Transfer Switch
Summary of Contents for HTS Wn
Page 16: ...14 Section 5 Notes HTS Wn Type Transfer Switch 14...
Page 17: ...15 Section 5 Notes HTS Wn Type Transfer Switch 15 15...
Page 18: ...16 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...
Page 19: ...17 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...
Page 20: ...18 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...
Page 21: ...19 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...
Page 22: ...20 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...
Page 23: ...21 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...
Page 24: ...22 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...
Page 25: ...23 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...
Page 26: ...24 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...
Page 27: ...25 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...
Page 28: ...26 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...
Page 29: ...27 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...
Page 30: ...28 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...
Page 31: ...29 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...
Page 34: ...32 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...
Page 35: ...33 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...