![Generac Power Systems HTS Wn Owner'S Manual Download Page 6](http://html1.mh-extra.com/html/generac-power-systems/hts-wn/hts-wn_owners-manual_2209792006.webp)
4
NOTE:
It is essential to use the latest version of any standard to ensure
correct and current information.
2.1 INTRODUCTION TO
INSTALLATION
This equipment has been wired and tested at the factory. Installing
the switch includes the following procedures:
Mounting the enclosure.
•
Connecting power source and load leads.
•
Connecting the generator communication circuit.
•
Setting DIP switches on ATS controller.
•
Programming Gxxx or Hxxx control on engine generator.
•
Installing/connecting any options and accessories.
•
Testing functions.
•
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely for any dam-
age that might have occurred during shipment. The purchaser
must file with the carrier any claims for loss or damage incurred
while in transit.
Check that all packing material is completely removed from the
switch prior to installation.
Attach any lifting device to the transfer switch mounting holes or
brackets only. DO NOT LIFT THE SWITCH AT ANY OTHER POINT.
2.3 MOUNTING
Mounting dimensions for the transfer switch enclosure are in this
manual. Enclosures are typically floor standing and mounted to
the wall. Components are generally mounted in a standard NEMA
12-type enclosure. A NEMA 3R, is also available. See TRANSFER
SWITCH OPTIONS section.
Handle transfer switches carefully when install-
ing. Do not drop the switch. Protect the switch
against impact at all times, and against con-
struction grit and metal chips. Never install a
transfer switch that has been damaged.
Install the transfer switch as close as possible to the electrical
loads that are to be connected to it. Stand the enclosure on a flat
surface. If the surface is not flat, it will be necessary to add shims
to make the enclosure level. Mount to a wall or support structure
for vertical stability. To prevent switch distortion, level all mounting
points. If necessary, use washers behind mounting holes to level
the unit.
2.4
CONNECTING POWER SOURCE
AND LOAD LINES
DANGER
Make sure to turn OFF both the NORMAL
(UTILITY) and STANDBY (EMERGENCY) power
supplies before trying to connect power source
and load lines to the transfer switch. Supply
voltages are extremely high and dangerous.
Contact with such high voltage power supply
lines causes extremely hazardous, possibly
lethal, electrical shock.
Wiring diagrams and electrical schematics are provided in this
manual. Power source and load connections are made at a transfer
mechanism, inside the switch enclosure.
2.4.1 TRANSFER MECHANISMS
The transfer mechanism may be either a 2-pole, 3-pole, or 4-pole
type (Figure 2.1). The switch enclosure may include a NEUTRAL
BLOCK for connection of the NEUTRAL line. Connect power source
and load leads to transfer mechanism terminal lugs as follows:
LOAD Leads: Connect to terminals T1, T2, T3, etc.
•
NORMAL (
•
UTILITY) Source Leads: To terminals N1, N2, N3,
etc.
STANDBY (
•
EMERGENCY) Source Leads: Connect to transfer
mechanism terminal lugs E1, E2, E3, etc.
Figure 2.1 — Transfer Mechanism
UTILITY
A
ON
B
STANDBY
OFF
A1
A2
B1
B2
AT1
AT2
BT2
BT1
64796
XXXXXX
600 VAC CSA
TRANSFER SWITCH
RATED CURRENT
480 VAC UL
RATED VOLTAGE
400 AMP
06
27
0
7-T
06
27
0
7-T
06
27
0
7-T
062707-
T
062707-
T
062707-
T
062707-T
-T
062707-T
T
Section 2 — Installation
HTS “Wn” Type Transfer Switch
Summary of Contents for HTS Wn
Page 16: ...14 Section 5 Notes HTS Wn Type Transfer Switch 14...
Page 17: ...15 Section 5 Notes HTS Wn Type Transfer Switch 15 15...
Page 18: ...16 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...
Page 19: ...17 Section 6 Mounting Dimensions 600 1000A NEMA 12 Drawing No 0F6963 D...
Page 20: ...18 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...
Page 21: ...19 Section 6 Mounting Dimensions 600 1000A NEMA 3R Drawing No 0F7314 D...
Page 22: ...20 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...
Page 23: ...21 Section 6 Mounting Dimensions 1200 1600A NEMA 12 Drawing No 0F7520 C...
Page 24: ...22 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...
Page 25: ...23 Section 6 Mounting Dimensions 1200 1600A NEMA 3R Drawing No 0F7521 C...
Page 26: ...24 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...
Page 27: ...25 Section 6 Mounting Dimensions 2000 2600A NEMA 12 Drawing No 0F8944 C...
Page 28: ...26 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...
Page 29: ...27 Section 6 Mounting Dimensions 2000 2600A NEMA 3R Drawing No 0F8945 C...
Page 30: ...28 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...
Page 31: ...29 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 208 240V Drawing No 0F7043 B...
Page 34: ...32 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...
Page 35: ...33 Section 7 Wiring Diagrams Electrical Schematics Wiring Diagram 480 600V Drawing No 0F7045 B...