16
Over Crank (Shutdown Alarm)
This occurs if the engine has not started within the specified crank
cycle. (See "Cranking" section.)
NOTE:
The oil drain hose may be routed in the opposite direction as
shown in figure.
Figure 3.5 – Low Oil Pressure and
High Temperature Switches
Oil Filter
Oil
Drain
Hose
Low Oil Switch
High Temp Switch
Loose
n
Over Speed (Shutdown Alarm)
4320 RPM for three (3) seconds or 4500 RPM immediately. This
feature protects the generator from damage by shutting it down
if it happens to run faster than the preset limit. This protection
also prevents the generator from supplying an output that could
potentially damage appliances connected to the generator circuit.
Contact the nearest Dealer if this failure occurs.
RPM Sense Loss (Shutdown Alarm)
During cranking, if the Control Board does not see a valid RPM
signal within three (3) seconds, it will shut down and lock out on
RPM sense loss. While engine is running, if RPM signal is lost for
one (1) second the Control Board will shut the engine down, wait
15 seconds, then re-crank the engine. If no RPM signal is detected
within the first three (3) seconds of cranking, the Control Board
will shut the engine down and latch out on RPM sensor loss. If the
RPM signal is detected, the engine will start and run normally. If
the RPM signal is subsequently lost again, the Control Board will
try one more re-crank attempt before latching out and displaying
the RPM sensor failure message.
Under-frequency (Shutdown Alarm)
After starting, if the generator stays under frequency for more than
30 seconds it will shut down. The under-frequency setting is 45
Hz.
Internal Fault (Shutdown Alarm)
This alarm cannot be cleared, call service dealer.
Undervoltage (Shutdown Alarm)
If the generator voltage falls below 60% of nominal for more than
five (5) seconds, it shuts down.
Overvoltage (Shutdown Alarm)
If the generator voltage rises above 110% of rating for greater than
three (3) seconds, an alarm will be issued and the unit will shut
down.
If the generator voltage rises above 130% of rating for greater than
0.2 seconds, an alarm will be issued and the unit will shut down.
Clear Alarm
Clear the alarm by setting the AUTO/OFF/MANUAL switch to the
OFF position. Press the ENTER key to unlatch any active fault and
clear the corresponding alarm message.
3.6.2
COMMON ALARM RELAY
The common alarm relay will be activated if there is a shutdown
alarm. It will not activate on warnings or indicate that the AUTO/
OFF/MANUAL switch is in the OFF position. The OFF position will
clear the alarms and the relay. The relay will not be used to indicate
a generator is not activated.
The common alarm terminals are wired to a set of potential-free
(dry) contacts on the Nexus contoller board. These Normally Open
(N.O.) contacts close when an alarm condition occurs and are
used to activate a remote signaling device. The circuit is rated for
a maximum of 130mA at 24 VDC.
3.6.3 WARNINGS
Second Priority (Non-latching) Displayed
on the control panel
and the external yellow LED (V-twins only). Warnings automati-
cally clear when the monitored condition goes away. Warnings are
recorded in the alarm log. Warnings cannot cause shutdowns.
Low Battery
The Control Board monitors battery voltage and displays a warn-
ing if the battery voltage falls below 11.9 volts for one (1) minute.
Warning is automatically cleared if the battery voltage rises above
12.4 volts. Battery voltage is not monitored during the crank cycle.
Exercise Set Error
If the exercise period becomes corrupted, a warning message
will be displayed. This message will only clear when the exercise
period is reset.
3.6.4 MAINTENANCE
ALERTS
Third priority
Operation
Summary of Contents for 0j2083
Page 30: ...28 Installation Diagrams Drawing No 0J3244 B ...
Page 31: ...29 Drawing No 0J3244 B Installation Diagrams ...
Page 32: ...Part No 0J2083 Revision G 04 02 13 Printed in U S A ...
Page 61: ...59 59 Notas ...
Page 62: ...Nº de parte 0J2083 Revisión G 02 04 13 Impreso en EE UU ...
Page 90: ...88 ДЛЯ ЗАМЕТОК ...
Page 91: ...89 89 ДЛЯ ЗАМЕТОК ...
Page 92: ... элемента 0J2083 Редакция G 04 02 13 Напечатано в США ...