Maintenance / Repairs
UA05
Replacing the position regulator
If a position regulator exchange was made, it is to be noted, that all
shielded cables are properly attached again!
WARNING
Electric shock hazard in contact with energized components
Keep the cover plate of the position regulator closed at all times!
► Before interventions take place in the device, the power supply
must be switched off!
► After switching off the power supply, wait at least 10 min. before
working on the equipment, because the internal condensers need
this time for discharging!
► Verify that the parts are deenergized by means of a voltmeter!