General safety regulations
OptiFeed B FPS19
Powder lying on the floor around the powder spraying equipment is a
potentially dangerous source of slipping. Booths may be entered only in
the places designed for this purpose.
Static charges
Static charges can have the following consequences: Charges to people,
electric shocks, sparking. Proper grounding must be in place to prevent
objects from becoming charged.
Grounding
All electrically conductive parts found within 5 meters around each booth
opening, and in particularly the objects to be coated, must be grounded.
The grounding resistance of each object must amount to maximally 1
MOhm. This resistance must be checked/tested regularly when starting
work.
The condition of the work piece attachments, as well as the hangers,
must guarantee that the work pieces remain grounded. The appropriate
measuring devices must be kept ready in the workplace, in order to
check the grounding.
The floor of the coating area must conduct electricity (normal concrete is
generally conductive).
The supplied grounding cable (green/yellow) must be connected to the
grounding screw of the Fresh powder system. The grounding cable must
have a good metallic connection with the coating booth, the recovery unit
and the conveyor chain, respectively with the suspension arrangement of
the objects.
Smoking and igniting fire are forbidden in the entire vicinity of the system!
No work that could potentially produce sparks is allowed!
Slip hazard
Observe the
grounding
regulations
Fire and smoke
prohibition