12.2 Process data
The motorized linear actuator has access to process data via the IO-Link. This is transmitted in cycles with every IO-Link tele-
gram.
Master
→
Device
Name
Bit
Values
Drive go Open
0
0
→
Actuator does not move into position Open
1
→
Actuator moves into position Open
Drive go Close
1
0
→
Actuator does not move into position Closed
1
→
Actuator moves into position Closed
Start initialization
2
0
→
No initialization
1
→
Start initialization
Locate
3
0
→
Off
1
→
On
Setpoint analog
8 … 23
Setpoint in the range 0 … 1000
Device
→
Master
Name
Bit
Values
Valve position Open
0
0
→
Process valve not in Open position
1
→
Process valve in Open position
Valve position Close
1
0
→
Process valve not in Closed position
1
→
Process valve in Closed position
Operating mode
2
0
→
Normal operation
1
→
Initialization mode
Valve position analog
8 … 23
Position of the valve in the range 0 … 1000
www.gemu-group.com
22 / 53
GEMÜ R563
12 Specific data IO-Link (pin 6)