12.4.29 Operating times
The current valve travel times can be read out with the
Operating times
parameter.
In-
dex
Sub
-
In-
dex
Off-
set
Access
Rights
Lengt
h
Index name
Parameter
Type
Default
Values
0x62
1
0
RO
8 bits
Operating times
Open
uint:8
0
0 to 255,
0 to 25.5 s
2
8
RO
8 bits
Close
uint:8
0
0 to 255,
0 to 25.5 s
Description of parameter values
Index name
Parameter
Values
Description
Operating times
Open
0 to 255
0 to 25.5 s
Read out operating time (in tenths of seconds) from end
position CLOSED to end position OPEN.
Close
0 to 255
0 to 25.5 s
Read out operating time (in tenths of seconds) from end
position OPEN to end position CLOSED.
12.4.30 Drive sets
The force of the actuator can be influenced with the
Drive sets
parameter when the valve is initialized and during initialization.
In-
dex
Sub
-
In-
dex
Off-
set
Access
Rights
Lengt
h
Index name
Parameter
Type
Default
Values
0x90
2
8
R/W
3 bits
Drive sets
Force
uint:16
-
1 … 6
3
16
R/W
3 bits
Force initializa-
tion
uint:16
-
1 … 6
Description of parameter values
Index name
Parameter
Values
Description
Drive sets
Force
1 … 6
Set the force of the valve. Preset at the factory depending on
the valve type.
Force initialization
1 … 6
Set the force during initialization. Preset at the factory
depending on the valve type.
Force settings
Actuator size
Setting parameter
Force
AG0 and AG1
1
Minimum force
6
Maximum force
www.gemu-group.com
40 / 53
GEMÜ R563
12 Specific data IO-Link (pin 6)