Description of parameter values
Index name
Parameter
Values
Description
Function digital inputs
Input 1
0
(Off)
Input without function.
1
(Open)
In case of the corresponding signal, the actuator
moves in the
OPEN
direction. If the other input (Digital Input
2) is configured as "Close", the actuator stops when the
inputs are not actuated. If the other input is not configured
as "Close", the actuator moves independently in the CLOSED
direction when the "Open" input is not actuated.
2
(Close)
In case of the corresponding signal, the actuator
moves in the
CLOSED
direction. If the other input (Digital
Input 2) is configured as "Open", the actuator stops when
the inputs are not actuated. If the other input is not
configured as "Open", the actuator moves independently in
the OPEN direction when the "Close" input is not actuated.
3
(Safe/On)
Safety position of the device is triggered. The
device operates normally if the signal is active. If there is no
signal, the device moves into the safety position. The safety
position is defined by the parameter Error Action (index 0x4F
(see "Error Action'").
4
(Init)
Input can be used as an initialization input.
Input 2
0
(Off)
Input without function.
1
(Open)
In case of the corresponding signal, the actuator
moves in the
OPEN
direction. If the other input (Digital Input
1) is configured as "Close", the actuator stops when the
inputs are not actuated. If the other input is not configured
as "Close", the actuator moves independently in the CLOSED
direction when the "Open" input is not actuated.
2
(Close)
In case of the corresponding signal, the actuator
moves in the
CLOSED
direction. If the other input (Digital
Input 1) is configured as "Open", the actuator stops when
the inputs are not actuated. If the other input is not
configured as "Open", the actuator moves independently in
the OPEN direction when the "Close" input is not actuated.
3
(Safe/On)
Safety position of the device is triggered. The
device operates normally if the signal is active. If there is no
signal, the device moves into the safety position. The safety
position is defined by the parameter Error Action (index 0x4F
(see "Error Action'").
4
(Init)
Input can be used as an initialization input.
GEMÜ R563
www.gemu-group.com
33 / 53