4. Push in new optical position indicator
S
until it is
fl
ush with the upper ring of
cap
K
.
K
A
H
S
®
The optical position indicator
S
is
completely assembled.
11.6 Functional test
1. Turn handwheel
H
to the left to check the
function of optical position indicator
S
:
A
K
S
H
®
The optical position indicator
S
moves
upwards like handwheel
H
.
2. Check tightness of completely
assembled diaphragm globe valve.
®
The diaphragm globe valve is ready for
use.
Important:
Service and maintenance:
Diaphragms degrade in the
course of time. After disassembly /
assembly of the diaphragm globe
valve check that the Allen bolts are
tight and retighten as necessary.
12 Commissioning
WARNING
Corrosive chemicals!
®
Risk of caustic burns!
G
Check the tightness of the
media connections prior to
commissioning!
G
Use only the appropriate
protective gear when
performing the tightness
check.
CAUTION
Protect against leakage!
G
Provide precautionary measures
against exceeding the maximum
permitted pressures caused by
pressure surges (water hammer).