6.6 Mechanical data
Protection class:
IP 65 acc. to EN 60529
Actuating speed:
Max. 2 mm/s
Flow direction:
Optional
Installation position:
Optional
Observe the angle of rotation to achieve an installation for optimized draining
Weight:
Actuator
MG 10: 0.8 kg
MG 20: 0.88 kg
MG 25: 0.94 kg
MG 40: 1.4 kg
Body
Connection
types
Code
1)
0, 30
20
28
7, 7R
33
3M,
3T
78
4, 39
1
75
2
MG
DN
10
12
-
-
-
-
-
-
-
-
0.08
-
0.06
15
-
-
0.13
0.18
0.13
-
-
-
-
0.08
-
20
-
-
-
-
-
-
-
-
-
0.125
-
20
15
0.12
0.10
-
0.17
0.24
0.26
0.27
0.67
-
-
-
20
0.13
0.12
-
0.21
0.28
0.30
0.36
0.84
-
-
-
25
0.16
0.14
-
0.26
0.33
0.38
0.37
1.28
-
-
-
25
32
0.22
0.18
-
0.40
0.70
0.73
0.63
1.89
-
-
-
40
40
0.50
0.40
-
0.73
0.83
0.93
1.13
2.36
-
-
-
50
0.57
0.47
-
1.00
1.40
1.50
1.60
3.08
-
-
-
Weights in kg
1)
Connection type
Code 0: Spigot DIN
Code 1: Threaded socket DIN ISO 228
Code 2: Solvent cement socket DIN
Code 3M: Union end with inch insert – ASTM (socket)
Code 3T: Union end with JIS insert (socket)
Code 4: Flange EN 1092, PN 10, form B, face-to-face dimension FTF EN 558 series 1, ISO 5752, basic series
1
Code 7: Union end with insert (socket) – DIN
Code 7R: Union end with insert (Rp threaded socket) - DIN
Code 20: Spigot for IR butt welding
Code 28: Spigot for IR butt welding, BCF
Code 30: Imperial butt weld spigot
Code 33: Union end with inch insert - BS (socket)
Code 39: Flange ANSI Class 125/150 RF, face-to-face dimension FTF EN 558 series 1, ISO 5752, basic
series 1, length only for body configuration D
Code 75: Flare connection with PVDF union nut
Code 78: Union end with insert (for IR butt welding) – DIN
6.7 Duty cycle and service life
Service life:
Class A acc. to EN 15714-2
Minimum 100,000 switching cycles at room temperature and permissible duty cycle.
Duty cycle:
max. 30% duty
GEMÜ R629 eSyLite
www.gemu-group.com
13 / 41
6 Technical data