www.gemu-group.com
33 / 41
GEMÜ R629 eSyLite
11 Operation
11.1 Manual override
WARNING
Damage to the product
▶
Risk of damage to the product
▶
Manufacturer liability and guarantee
will be void.
●
Only operate the manual override
by
hand
because there is no mechanical
stop.
1
2
1. Remove the sealing plug
2
from the actuator cover
1
using
an appropriate tool.
3
OPEN
CLOSED
2. Operate the manual override
3
with the hexagon socket
(WAF3).
ð
Turn clockwise to close the valve.
ð
Turn anticlockwise to open the valve.
12 Inspection and maintenance
WARNING
The equipment is subject to pressure!
▶
Risk of severe injury or death.
●
Depressurize the plant.
●
Completely drain the plant.
CAUTION
Use of incorrect spare parts!
▶
Damage to the GEMÜ product.
▶
Manufacturer liability and guarantee will be void.
●
Use only genuine parts from GEMÜ.
CAUTION
Hot plant components!
▶
Risk of burns.
●
Only work on plant that has cooled
down.
NOTICE
Exceptional maintenance work!
▶
Damage to the GEMÜ product.
●
Any maintenance work and repairs not described in these
operating instructions must not be performed without
consulting the manufacturer first.
The operator must carry out regular visual examination of the
GEMÜ products depending on the operating conditions and
the potential danger in order to prevent leakage and damage.
The product also must be disassembled and checked for
wear in the corresponding intervals.
1. Have servicing and maintenance work performed by
trained personnel.
2. Wear appropriate protective gear as specified in plant op-
erator's guidelines.
3. Shut off plant or plant component.
4. Secure plant or plant component against recommission-
ing.
5. Depressurize the plant or plant component.
6. Actuate GEMÜ products which are always in the same po-
sition four times a year.
7. If necessary, the end position counter
User
can be reset
after maintenance or other changes under parameter
Cycle Counter.
12 Inspection and maintenance