12.4.31 Operating times
The current valve travel times can be read out with the
Operating times
parameter.
Index Sub-
In-
dex
Off-
set
Access
Rights
Length
Index name
Parameter
Type
Default
Values
0x62
1
0
RO
8 bits
Operating times
Open
uint:8
0
0 to 255,
0 to 25.5 s
2
8
RO
8 bits
Close
uint:8
0
0 to 255,
0 to 25.5 s
Description of parameter values
Index name
Parameter
Values
Description
Operating times
Open
0 to 255
0 to 25.5 s
Read out operating time (in tenths of seconds) from end pos-
ition CLOSED to end position OPEN.
Close
0 to 255
0 to 25.5 s
Read out operating time (in tenths of seconds) from end pos-
ition OPEN to end position CLOSED.
12.4.32 Drive sets
The traverse speed and force of the actuator can be influenced with the
Drive sets
parameter when the valve is initialized.
Index Sub-
In-
dex
Off-
set
Access
Rights
Length
Index name
Parameter
Type
Default
Values
0x90
1
0
R/W
2 bits
Drive sets
Speed
3
1 … 3
2
8
R/W
3 bits
Force
-
1 … 6
Description of parameter values
Index name
Parameter
Values
Description
Drive sets
Speed
1 … 3
Select the speeds for the average travel range.
Force
1 … 6
Set the force for the average travel range and for sealing.
Preset at the factory depending on the valve type.
Speed
Actuator size
Setting parameter
Average speed in mm / s
AG0 and AG1
1 (43 %)
1.6
2 (71 %)
2.3
3 (100 %)
3.0
Force settings
Actuator size
Setting parameter
Force
AG0 and AG1
1
Minimum force
6
Maximum force
12.5 Events
The following IO-Link events can be transmitted.
Event
Mode
Type
Code
Device Hardware Fault
App/Disapp
Error
0x5000
Motor Unable To Move
App/Disapp
Error
0x8CE0
Device Temperature Over-Run
App/Disapp
Warning/Error
0x4210
Emergency Power
App/Disapp
Warning
0x5100
Primary Supply Voltage Under-Run
App/Disapp
Error
0x5111
www.gemu-group.com
54 / 67
GEMÜ 639 eSyStep
OPEN / CLOSE (Code AE)
12 Specific data IO-Link (pin 6)