Index Sub-
Index
Access
rights
Index name
Parameter
Function
Factory
settings
Setting options
0x18
0
R/W
Application specific
tag
Text with 32 charac-
ters can be entered
„****************“
0x19
0
R/W
Function tag
Text with 32 charac-
ters can be entered
„****************“
0x1A
0
R/W
Location tag
Text with 32 charac-
ters can be entered
„****************“
0x24
0
RO
Device status
(Simple) device
status
0
→
Operating prop-
erly
2
→
Out of specific-
ation
4
→
Failure
0x25
0
RO
Device status
Detailed device
status
0x40
0
RO
Actuator size
Read out actuator
size
Depending on
the actuator
size used
0
→
Actuator size 0
1
→
Actuator size 1
2
→
Actuator size 2
0x4B
1
R/W
Function digital in-
puts
Input 1
Configure digital in-
put 1
1
0
→
Off
1
→
Open
2
→
Close
3
→
Safe/On
4
→
Init
2
R/W
Input 2
Configure digital in-
put 2
2
0
→
Off
1
→
Open
2
→
Close
3
→
Safe/On
4
→
Init
0x4C
1
R/W
Function digital in-/
output 1
In- / output 1
Configure digital in-
puts/outputs
0
0
→
Output open
1
→
Output close
2
→
Output error
3
→
Output error &
warning
4
→
Input init
2
R/W
Type in- / output 1 Configure type of di-
gital inputs/outputs
0
0
→
Push-pull
1
→
NPN
2
→
PNP
0x4D
0
R/W
Function digital out-
put 2
Configure digital
output
1
0
→
Output open
1
→
Output close
2
→
Output error
3
→
Output error &
warning
0x4E
1
R/W
Logic digital inputs /
outputs
Input 1
Configure logical di-
gital input 1
0
0
→
Active high
1
→
Active low
2
R/W
Input 2
Configure logical di-
gital input 2
0
0
→
Active high
1
→
Active low
3
R/W
Input / output 1
Configure logical di-
gital input/output
0
0
→
Active high
1
→
Active low
4
R/W
Output 2
Configure logical di-
gital output
0
0
→
Active high
1
→
Active low
GEMÜ 639 eSyStep
OPEN / CLOSE (Code AE)
www.gemu-group.com
37 / 67
12 Specific data IO-Link (pin 6)