11.3 Overview of available functions – Input and output signals
NOTICE
▶
The factory default setting "Configured for emergency power supply module" is reset to default settings when a reset is car-
ried out.
NOTICE
▶
When configuring the emergency power module (code A5 / A6), the control of the valve changes. Valve is controlled 1-pole
via digital input 1. Level logic 1 moves the valve OPEN, level logic 0 moves the valve CLOSE.
Function
Control module AE
Control module A5, A6
Default settings
Factory default setting
"Configured for emergency
power supply module"
Digital input 1
Off/Open/Closed/Safe/On/
Initialization
Open
Open
Digital input 2
Off/Open/Closed/Safe/On/
Initialization
Closed
Safe/On
Digital input/output
Open/Closed/Error/Error and
warning/Initialization
Open
Open
Digital output
Open/Closed/Error/Error and
warning
Closed
Closed
GEMÜ 639 eSyStep
OPEN / CLOSE (Code AE)
www.gemu-group.com
31 / 67