Place the logic element NOT, with adapter plate and seal, on the pneumatic
block (8) as shown in the illustration.
!
When inserting and tightening the screws, be careful to use existing threads.
Fig.66
®
Done
Hint!
Faulty assembly may cause malfunctions, as the spring force backup
is then not given.
10.5.8 Removing the Solenoid Valves and the Control Plate
Fig.67
Requirement:
•
Pay attention to the correct assignment of cables between the solenoid valves
and the circuit board (9) – solenoid valve Y1 must be connected to terminal
Y1; solenoid valve Y2 to terminal Y2 and solenoid valve Y3 to terminal Y3.
•
Use only solenoid valves as listed in the chapter "Technical data", see
Chapter 5, Page 23.
Maintenance
Dismantling the Control Top into its Components
430BAL010699EN_6
90
17.03.2022