Chapter 4. Ladder Diagram (LD) Programming
94
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual
GFK-2950C
4.4.3
High and Low Alarm Contacts
The
high alarm contact
(HIALR) is used to detect a high alarm associated with an analog reference.
Use of this contact and the low alarm contact must be enabled during CPU configuration.
A high alarm contact passes power flow if the high alarm bit associated with the analog reference is
ON.
The
low alarm contact
(LOALR) detects a low alarm associated with an analog reference. Use of
this contact must be enabled during CPU configuration.
A low alarm contact passes power flow if the low alarm bit associated with the analog reference is
ON.
Operands
Parameter Description
Allowed Operands
Optional
WORDV
The variable associated with the HIALR or LOALR
contact
variables in AI and AQ
memories
No