Chapter 4. Ladder Diagram (LD) Programming
76
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual
GFK-2950C
Operands for Logical AND, OR, and XOR
Parameter
Description
Allowed Operands
Optional
Length (??)
The number of words in the bit string
on which to perform the logical
operation. 1
Length
256.
Constant
No
IN1
The first WORD or DWORD of the
first string operate on.
All
No
IN2 (Must be the same
data type as IN1.)
The first WORD or DWORD of the
second string to operate on.
All
No
Q (Must be the same data
type as IN1.)
The first WORD or DWORD of the
operation’s result.
All except constants and
variables located in %S memory
No
Example: Logical AND
When input v_I0001 is set, the 16-bit strings represented by variables WORD1 and WORD2 are
examined. The logical AND places the results in output string RESULT.
Example: Logical XOR
Whenever V_I0001 is set, the bit string represented by the variable WORD3 is cleared (set to all
zeroes).