DISTRIBUTED DIGITAL FAULT RECORDER – INSTRUCTION MANUAL
CONFIGURING THE DDFR WATCHDOGS
CHAPTER 3: DDFR CONFIGURATION
2.
Perform automated maintenance when 'Used Space' capacity of Local Disk
exceeds 80%
When the DDFR’s used storage space exceeds this level, the automated
maintenance starts deleting the oldest records.
3.
Automated maintenance occurs until 'Used Space' capacity of Local Disk
drops below 70%
This setting indicates the level of used storage space that the DDFR will
recover to before the automated maintenance stops.
3.4.3.2 Adding a DriveSpace WatchDog
A DriveSpace WatchDog must be configured in both the DDFR and the (UR) relay intended
as the receiver of the WatchDog. The following will show the configuration of a DriveSpace
WatchDog within the DDFR.
Z
Press the
Insert
key on your keyboard.
Each time you press this key, you will add a line to the External
section of the WatchDog window, as shown in Figure 3-13.
Z
Each time you add a line, select a device (UR relay) by clicking on
the
Device
pull-down list located in the cell on that line, and
selecting the appropriate relay.
FIGURE 3–13: Selecting a Device (relay)
Z
Similarly, select the
Virtual Input
to be used on the device (relay)
by clicking on the
Virtual Input
pull-down list as shown in Figure
3-14.