6–82
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION
CHAPTER 6: SETPOINTS
BLOCK 1/2/3
Range: Off, Contact Input 1 to 10[8], Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16
Default: Off
Three blocking inputs are provided in the Neutral IOC menu. One blocking input going
“high” is enough to block the function. The selection for each block can be Contact input,
Virtual Input, Remote Input, or Logic Element.