9-30
MIFII Digital Feeder Relay
GEK-106237P
9.19 USER SETTINGS
9 RELAY COMMISSIONING
9
ENERVISTA MII SETUP HMI
USER
SETTING
RANGE
STEP
50 G1 Pickup (1/5 A
ground)
Pickup 50G1
Pickup 50G1
0.1 – 30 In (Gnd)
0.1 In (G)
50 G1 Pickup Value
(sensitive ground)
Pickup 50G1
Pickup 50G1
0.005-0.12 A
0.001 A
50 G1 Time Delay
Delay 50G1
Delay 50G1
0.00 – 600.00 s.
0.01 s.
Gnd IOC Low Set
group 2
GROUND IOC 50G2
(group 2)
Ground IOC 50G2
50G2 Permission to
Trip
Trip Enable 50G2
Trip Enable 50G2
Yes/No
NA
50G2 Pickup (1/5 A
ground)
Pickup 50G2
Pickup 50G2
0.1 – 30 In (Gnd)
0.1 In (G)
50G2 Pickup Value
(sensitive ground)
Pickup 50G2
Pickup 50G2
0.005-0.12 A
0.001 A
50G2 Time Delay
Delay 50G2
Delay 50G2
0.00 –600.00s.
0.01 s.
Thermal Image group
2
49 Function (group 2)
THERMAL MODEL
49
Permission to Trip
Trip Enable 49
Trip Enable 49
Yes/No
NA
49 Pickup
Pickup 49
Pickup 49
0.10 – 2.40 In (Ph)
0.01 In
(Ph)
Overload Percent
Alarm
Alarm Level 49
Alarm Level 49
70% – 100% ITH
Heating Time
Constant
τ
1
Heat Time 49
Heat Time 49
3 – 600 min.
1 min.
Cooling Time
Constant
τ
2
Cool Time 49
Cool Time 49
1– 6 times
τ
1
1
Parameters
User Curve
User Curve
A
A Parameter
A Parameter
0.0000-125.0000
0.0001
B
B Parameter
B Parameter
0.0000-3.0000
0.0001
P
P Parameter
P Parameter
0.0000-3.0000
0.0001
Q
Q Parameter
Q Parameter
0.0000-2.0000
0.0001
K
K Parameter
K Parameter
0.000-1.999
0.001
Counter
I^2 MAX Value
I
2
limit
Maximum Counter
I
2
T MAX
0.000-999.000 kA2
0.001
kA2
Breaker failure to
open
Breaker failure to open
Breaker failure to
open enable
Breaker failure function
Function
Y/N
NA
Fail to open timer
Fail to open timer
Delay
50-999 ms
1 ms
Cold load pickup
Cold load pickup
CLP
Cold load pickup
enable
Cold load pickup
function
Function
Yes/No
NA
Pickup time
T IN
Outage Time
0.000-60.000 s
0.001 s
Drop out time
T OUT
On Load Time
0.000-60.000 s
0.001 s
Constant. 50P pickup K 50P
Phase IOC Mult
1.00-5.00
0.01
Constant 51P pickup K 51P
Phase TOC Mult
1.00-5.00
0.01
Summary of Contents for MIFII GEK-106237P
Page 91: ...4 28 MIFII Digital Feeder Relay GEK 106237P 4 7 VIEW 4 COMMUNICATIONS 4 ...
Page 124: ...GEK 106237P MIFII Digital Feeder Relay 8 7 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 8 5MENU TREE ...
Page 125: ...8 8 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 126: ...GEK 106237P MIFII Digital Feeder Relay 8 9 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 127: ...8 10 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 128: ...GEK 106237P MIFII Digital Feeder Relay 8 11 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 129: ...8 12 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 130: ...GEK 106237P MIFII Digital Feeder Relay 8 13 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 131: ...8 14 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 185: ...A 10 MIFII Digital Feeder Relay GEK 106237P A 6 MIFII THERMAL CURVES APPENDIXA A ...
Page 203: ...B 18 MIFII Digital Feeder Relay GEK 106237P B 3 IAC CURVES APPENDIXB B ...
Page 245: ...F 8 MIFII Digital Feeder Relay GEK 106237P F 5 CONCLUSIONS APPENDIXF F ...