9-26
MIFII Digital Feeder Relay
GEK-106237P
9.19 USER SETTINGS
9 RELAY COMMISSIONING
9
9.19USER SETTINGS
The following pages intend to be useful to register the user settings. They can be used as a guide or template or to record
the relay settings.
9.19.1 MAIN SETTINGS
ENERVISTA MII SETUP HMI
USER
SETTING
RANGE
STEP
PRODUCT SETUP
PRODUCT SETUP
PRODUCT SETUP
Relay Status
Relay Operation
Relay Operation
READY / DISABLE
NA
Frequency
Frequency
Frequency
50/60 Hz
NA
Phase CT ratio
Phase CT Ratio
Phase CT Ratio
1-4000
1
Ground CT ratio
Ground CT Ratio
Ground CT Ratio
1-4000
1
HMI Password
---
HMI Password
0-9999
1
Comm Password
---
Comm Password
1 – 255
1
Slave Address
---
Slave Address
1 – 255
1
Communications Speed
---
Comm Baud Rate
0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2
NA
Phase TOC Function
PHASE TOC 51P
PHASE TOC 51P
51P Permission to Trip
Trip Enable 51P
Trip Enable 51P
Yes/No
NA
51P Pickup Value
Pickup 51P
Pickup 51P
0.1-2.4 In (Ph)
0.01 In (Ph)
51P Curve Type
Curve 51P
Curve 51P
DEFINITE TIME, USER, MOD
INVERSE, VERY INVERSE,
EXTR INVERSE, INVERSE
LONG, INVERSE SHORT
NA
51P Time Dial
TD mult 51P
TD mult 51P
0.05 – 2.00 (IEC curves)
0.01
0.5 – 20.0 (ANSI curves)
0.01
0.5 – 10.0 (IAC curves)
0.01
51P Definite Time Delay
Def Time 51P
Def Time 51P
0.00 – 600.00 s.
0.01 s.
Ground TOC Function
GROUND TOC 51G
GROUND TOC 51G
51G Permission to Trip
Trip Enable 51G
Trip Enable 51G
Yes/No
NA
51G Pickup (for 1/5 A
ground)
Pickup 51G
Pickup 51G
0.10 – 2.40 In (Gnd)
0.01 In
(Gnd)
51G Pickup (for sensitive
ground)
Pickup 51G
Pickup 51G
0.005-0.12 A
0.001 A
51G Curve Type
Curve 51G
Curve 51G
DEFINITE TIME, USER, MOD
INVERSE, VERY INVERSE,
EXTR INVERSE, INVERSE
LONG, INVERSE SHORT
NA
51G Time Dial
TD Mult 51G
TD Mult 51G
0.05 – 2.00 (IEC curves)
0.01
0.5 – 20.0 (ANSI curves)
0.01
0.5 – 10.0 (IAC curves)
0.01
51G Definite Time Delay
Def Time 51G
Def Time 51G
0 –600.00s.
0.01 s.
Phase IOC High Setting
50P1 Function
Phase IOC 50P1
50P1 Permission to Trip
50P1 Trip
Trip Enable 50P1
Yes/No
NA
50P1 Tap / Pickup
50P1 Pickup
Pickup 50P1
0.1 – 30.0 In (Ph)
0.1 In (Ph)
50P1 Time Delay
50P1 Time Delay
Delay 50P1
0 – 600.00 s.
0.01 s.
Phase IOC Low Setting
50P2 Function
Phase IOC 50P2
50P2 Permission to Trip
50P2 Trip
Trip Enable 50P2
Yes/No
NA
50P2 Tap / Pickup
50P2 Pickup
Pickup 50P2
0.1 – 30.0 In (Ph)
0.1 In (Ph)
50P2 Time Delay
50P2 Time Delay
Delay 50P2
0 – 600.00 s.
0.01 s.
Ground IOC High Set.
50G1 Function
Ground IOC 50G1
50G1 Permission to Trip
50G1 Trip
Trip Enable 50G1
Yes/No
NA
50G1 Tap / Pickup (for 1/5
A ground)
50G1 Pickup
Pickup 50G1
0.1 – 30 In (Gnd)
0.1 In (G)
Summary of Contents for MIFII GEK-106237P
Page 91: ...4 28 MIFII Digital Feeder Relay GEK 106237P 4 7 VIEW 4 COMMUNICATIONS 4 ...
Page 124: ...GEK 106237P MIFII Digital Feeder Relay 8 7 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 8 5MENU TREE ...
Page 125: ...8 8 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 126: ...GEK 106237P MIFII Digital Feeder Relay 8 9 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 127: ...8 10 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 128: ...GEK 106237P MIFII Digital Feeder Relay 8 11 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 129: ...8 12 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 130: ...GEK 106237P MIFII Digital Feeder Relay 8 13 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 131: ...8 14 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 185: ...A 10 MIFII Digital Feeder Relay GEK 106237P A 6 MIFII THERMAL CURVES APPENDIXA A ...
Page 203: ...B 18 MIFII Digital Feeder Relay GEK 106237P B 3 IAC CURVES APPENDIXB B ...