9-16
MIFII Digital Feeder Relay
GEK-106237P
9.15 PHASE TOC ELEMENT (51P)
9 RELAY COMMISSIONING
9
9.15.4 ANSI INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current into phase A and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 36.2 and 51.3 sec.
Apply 5 times the pickup current and the relay should trip between 3.9 and 4.3 sec.
9.15.5 ANSI VERY INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current into phase B and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 26.7 and 37.3 sec.
Apply 5 times the pickup current and the relay should trip between 2.4 and 2.8 sec.
9.15.6 ANSI EXTREMELY INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current into phase C and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 17.2 and 23.6 sec.
Apply 5 times the pickup current and the relay should trip between 1.7 and 1.35 sec.
9.15.7 IAC INVERSE CURVE
Set the relay as follows:
Apply 0.9 times the pickup current at the ground terminals and the relay should not trip.
Apply 1.5 times the pickup current and the relay should trip between 10.86 and 12.25 sec.
Apply 5 times the pickup current and the relay should trip between 3.69 and 4.16 sec.
51P SETTINGS GROUP
Curve
INVERSE
Time Dial
10
51P SETTINGS GROUP
Curve
VERY INVERSE
Time Dial
10
51P SETTINGS GROUP
Curve
EXTREMELY INVERSE
Time Dial
5
51P SETTINGS GROUP
Curve
INVERSE
Time Dial
10
Summary of Contents for MIFII GEK-106237P
Page 91: ...4 28 MIFII Digital Feeder Relay GEK 106237P 4 7 VIEW 4 COMMUNICATIONS 4 ...
Page 124: ...GEK 106237P MIFII Digital Feeder Relay 8 7 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 8 5MENU TREE ...
Page 125: ...8 8 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 126: ...GEK 106237P MIFII Digital Feeder Relay 8 9 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 127: ...8 10 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 128: ...GEK 106237P MIFII Digital Feeder Relay 8 11 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 129: ...8 12 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 130: ...GEK 106237P MIFII Digital Feeder Relay 8 13 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 131: ...8 14 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 185: ...A 10 MIFII Digital Feeder Relay GEK 106237P A 6 MIFII THERMAL CURVES APPENDIXA A ...
Page 203: ...B 18 MIFII Digital Feeder Relay GEK 106237P B 3 IAC CURVES APPENDIXB B ...
Page 245: ...F 8 MIFII Digital Feeder Relay GEK 106237P F 5 CONCLUSIONS APPENDIXF F ...