9-18
MIFII Digital Feeder Relay
GEK-106237P
9.15 PHASE TOC ELEMENT (51P)
9 RELAY COMMISSIONING
9
9.15.12 DEFINITE TIME
Set the relay as follows:
Apply 0.9 times the pickup current into phase A and the relay should not trip.
Apply 1.1 times the pickup current and the relay should trip in 1.0 sec. Acceptable time range is between 1.00 and 1.06 sec.
Apply 4 times the pickup current and the relay should trip in 1.0 sec. Acceptable time range is between 1.00 and 1.06 sec.
51P SETTINGS GROUP
Curve
DEFINITE TIME
Definite Time Delay
1.0
Summary of Contents for MIFII GEK-106237P
Page 91: ...4 28 MIFII Digital Feeder Relay GEK 106237P 4 7 VIEW 4 COMMUNICATIONS 4 ...
Page 124: ...GEK 106237P MIFII Digital Feeder Relay 8 7 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 8 5MENU TREE ...
Page 125: ...8 8 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 126: ...GEK 106237P MIFII Digital Feeder Relay 8 9 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 127: ...8 10 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 128: ...GEK 106237P MIFII Digital Feeder Relay 8 11 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 129: ...8 12 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 130: ...GEK 106237P MIFII Digital Feeder Relay 8 13 8 KEYPAD AND DISPLAY 8 5 MENU TREE 8 ...
Page 131: ...8 14 MIFII Digital Feeder Relay GEK 106237P 8 5 MENU TREE 8 KEYPAD AND DISPLAY 8 ...
Page 185: ...A 10 MIFII Digital Feeder Relay GEK 106237P A 6 MIFII THERMAL CURVES APPENDIXA A ...
Page 203: ...B 18 MIFII Digital Feeder Relay GEK 106237P B 3 IAC CURVES APPENDIXB B ...
Page 245: ...F 8 MIFII Digital Feeder Relay GEK 106237P F 5 CONCLUSIONS APPENDIXF F ...