8.6
Unable to Download to Controller or I/O Module
If intermittent communication loss occurs between the HMI and the controllers, the downloading process could be interrupted
at intermediate stages. It is recommended that the download be carried out for base load, firmware, and
application/parameters individually to the controllers and the I/O packs. Firmware download to the controllers could be
interrupted due to issues related to incorrect library references.
The Model Predictive Control (MPC) block libraries are not supported by the UCSA/UCSB/UCSC controller. Therefore, if
the application is configured for the UCSA/UCSB/UCSC controller and the MPCBlockLib is used as a reference library, the
firmware download is interrupted.