8.9.4
Mismatched Revision
A revision mismatch is indicated by a ≠ icon on the I/O module Status tab.
➢
➢
To resolve a revision mismatch
1.
From the
Component Editor Device
menu, select
Download
and
Download Wizard
.
2.
From the wizard page, select
Next
and scan the I/O module to verify that all unequal items are selected for download.
3.
Perform a Download to the I/O module. When the Download is complete, wait for the I/O module to go online and verify
that all revisions are equal.
Attention
If the configuration being downloaded contains I/O modules with different module IDs
than the configuration currently running, the download may install incorrect
firmware to some I/O modules. If this occurs, make sure the controller is running the
new configuration, restart the entire system, then start the ToolboxST Download
Wizard again.