A-2
6" QuickPanel* ViewBasic, Monochrome, Round Bezel – September 2010
GFK-2327B
A
DC Power
Input Voltage
12 to 30 VDC
Power Dip Tolerance
-30% nominal input voltage, 10msec.
Insulation Resistance
268Mohm @ 1000V frame ground to 0V
366Mohm @ 1000V frame ground to 24V
Real Power
9 W
Power requirement nominal for startup when DC supply
is already powered and stable. Applying power to the
supply while connected to the QuickPanel View
increases total inrush current requirements. In this case,
supply should be rated at 10x the nominal startup
current. Otherwise, an interposing relay or switch must
be used between the DC supply and the QuickPanel
View.
NOTE: For compliance with UL 1604, switches or relays
inline with the DC power wiring cannot be used in
hazardous locations.
Connector (Vendor, p/n)
Phoenix Contact,
1777992
NOTE
:
The torque range for the attaching screws is 4-6
inch/lbs.
Power Supply Conductor Size
12 to 18 AWG
For compliance to CE Mark, the isolated frame ground
must be connected.
Recommended frame ground connection is via the
shortest possible route, using 14 AWG.