1-6
6" QuickPanel* ViewBasic, Monochrome, Round Bezel – September 2010
GFK-2327B
1
Panel Cutout
For enclosure mounting, cut an opening in the panel according to the following
specifications.
Depth 2.026” (51.5mm)
Notes:
For compliance to NEMA 4, 4x, and 12 qualification, the unit must be
mounted in a comparably NEMA rated (IP56 equivalent) panel or
enclosure.
For compliance to ATEX agency qualification, the unit must be mounted in
an IP66 panel or enclosure.
To avoid gasket degradation, limit repeated insertions or removals of the
unit and retightening of the mounting clips. For full protection, always use a
fresh gasket. Replacement gaskets may be ordered using part number
IC754ACC06GAS.
Summary of Contents for IC754VSB06MTD
Page 4: ......
Page 8: ......
Page 19: ...GFK 2327B Chapter 2 Overview 2 3 2 Physical Layout of QuickPanel View...
Page 66: ......
Page 74: ......