Hydran* 201
i
Installation Guide
Page 30
17996 Rev5, August 2013
5.7
Fastening the Hydran 201Ti to the Brass Adaptor
1.
Using the supplied 3/16-in Allen key, fasten the H201Ti’s heating plate to the
brass adaptor with the six 1/4-28 cap screws. See Figure 17 below.
Figure 17: Fastening the Heating Plate to the Brass Adapter
Be careful not to squeeze the nearby electrical wires between
the lock washers
and the heating plate or not to damage the
supervisory link (and analog output) termination board.
Note: When the H201Ti is installed horizontally, the terminals must be facing up
and located under the sensor. Also, ensure that both the bleed screw and
sampling port remain easy to access.
2.
Plug the twist-lock female connector of the sensor cable to the male
connector behind the Hydran 201 sensor,
CAUTION