Hydran* 201
i
Installation Guide
Page 24
17996 Rev5, August 2013
6.
The total distance between the H201T
i
and the mounting point of the valve
must not
exceed six times the nominal diameter of the valve
(230mm [9 in] for
a 38mm
[1.5in] valve). See Figure 14 below.
Figure 14: Maximum Distance between the Hydran 201
Ti
and the Valve
7.
The H201T
i
weighs 5.6kg (12lb). If the selected valve is subject to strong
vibrations, install a supporting bracket to reduce the load on the valve.
In
case of doubt, consult
your engineering personnel.