![GE Hydran 201i Installation Manual Download Page 20](http://html.mh-extra.com/html/ge/hydran-201i/hydran-201i_installation-manual_128388020.webp)
Page 21
Hydran* 201
i
Installation Guide
17996 Rev5, August 2013
10.
Install the H201Ti horizontally; not at an angle, vertically or horizontally using
an elbow
(see Figure 10 below). Elbows may cause turbulence that can
reduce the
accuracy of gas level readings.
Figure 10: Do Not Install the H201T
i
on an Elbow
11.
Do not subject the H201Ti or its sensor to high-pressure water streams
(see
Figure 11 below). Used during the cleaning of transformers, they may cause
serious damage.
Figure 11: Avoid High Pressure Water Streams
12.
Do not punch additional openings in the H201Ci Controller’s enclosure
. This
enclosure already has openings for the various cables used with the Hydran
201
i
System.