background image

 

Backpulse Tank Pressure Check

Using the Digital Air Pressure Gauge, check the 

Backpulse Tank pressure. If it is not at the correct pressure 

(Approximately 35 psi for most installations; 

Refer to the 

Service Tag for the actual reading), adjust the pressure 

using an air pump or compressor.  Refer to Step 3 of the 

System installation

 section under

E. inSTallaTiOn inSTrUCTiOnS

 for guidance.

2

 

G. annUal MainTEnanCE

To extend the life of the System’s membrane, maintenance 

procedures are recommended on a minimum of an annual 

basis. A Service Kit is required, including an Integrity 

Tester and other necessary tools, to perform the Annual 

Maintenance.  A 

Homespring™ Qualified Technician 

 

must perform all maintenance including the annual 

Integrity Test as required as part of the 5 year limited 

prorated System warranty.  If the 

Homespring™ Qualified 

Technician 

determines that the System has a high degree 

of debris causing a reduction in the flowrate, the number 

of maintenance visits per year may be increased to ensure 

that the System stays within operational limits, and to 

ensure the limited prorated warranty protection remains in 

effect.

annual Maintenance Procedure

 

Transmembrane Pressure Test

 

The first step will be to perform a “pre-cleaning” trans-

membrane pressure test. To perform this test, follow 

the 

steps in the 

Transmembrane Pressure Test

 section under 

f. COMMiSSiOninG

. Thi

s test will be performed prior to 

the cleaning and again following the Integrity Test. The 

results of these tests are to be recorded on the Service 

Tag.

If the Inlet Valve is upstream of the External Prefilter, 

change the External Prefilter follo

wing guidelines

 in the 

Surface Water Option Kit installation

 

section under

E. inSTallaTiOn inSTrUCTiOnS

 to install a new 

External Prefilter cartridge before beginning the Membrane 

Cleaning.

1

 

3

 

membrane cleaning

WARNING!

Disposable protective gloves must be worn during 

maintenance of the System to protect your hands.  

At the end of the procedure, wash your hands 

thoroughly with soap and water. Do not reuse the 

gloves. Dispose of the gloves in the garbage. 

complete Paperwork

The following documents are shipped with the System:

Owner’s Manual

Congratulations letter

Installation Checklist

Service Tag

Warranty Card

Pipe Labels

• Complete all info on the Service Tag and hang from 

System Cap.

• Complete and return the Installation/Registration 

Checklist, ensure that all fields are complete, including the 

homeowner’s signature.

 Record the model number on page 2 of the Owner’s 

Manual 

for future reference.

final flush by Homeowner

Have the homeowner continue to run a cold water tap for 

60 minutes.  This is required to meet NSF drinking water 

standards and to remove residual chlorine. The homeowner 

may notice chlorine taste/smell when a tap is first opened 

for a day or two following the cleaning procedure.

Transmembrane Pressure (TMP) Test

The  TMP  test  measures  the  pressure  drop  across 

the  membrane.  This  is  the  pressure  change  that  the 

homeowner  will  observe  as  a  result  of  the  filtering 

process. The TMP is tracked during the life of the System 

and  is  used  to  determine  the  condition  of  the  System 

membrane. As the membrane fouls, the TMP will increase.

2

 

 

With a nearby tap running with a high flow rate, 

read the two Pressure Gauges and subtract the Outlet 

pressure from the Inlet pressure. The resulting value is the 

TMP.  Record the value on the Service Tag.

When a pump/pressure tank is in use, use the following 

inlet pressure to determine TMP:

1

 

 

Insert a Pressure Gauge into each of the Inlet and 

Outlet Mini Ball Valves and open the valves.

fiGUrE 46 

For  installations  excluding  ground  water  installations, 

clean  the  membrane  following  the  steps 

in  the 

cleaning

 

section  under 

f.  COMMiSSiOninG

  with  the  following 

exceptions.  In  Step 

3,

  after  the  System  Cap  is  removed, 

wipe the System Cap out with a clean, soft cloth, remove 

the  O-ring  carefully,  wipe  the  O-ring  with  a  clean  cloth, 

check  the  O-ring  for  damage  or  wear,  apply  a  very  small 

amount  of  DOW  CORNING  111  silicone  lubricant  on  the  

23

Summary of Contents for Homespring UFC 100

Page 1: ...8 23 G ANNUAL MAINTENANCE Pages 23 24 H WINTERIZATION Pages 25 27 I TROUBLESHOOTING Pages 28 29 J SPECIFICATIONS Pages 30 31 K FAQ Pages 32 33 L REPLACEMENT PART LIST AND PROCEDURES Pages 34 42 Operat...

Page 2: ...d when installing or servicing the filtration system System Failure to do may result in System damage serious personal in jury death and or property damage Use of non OEM parts will void the manufactu...

Page 3: ...ion Bypass Procedure 1 Close Inlet and Outlet Valves If ball valves are installed turn the handles perpendicular to the water pipe 2 Open Bypass Valve If ball valve is in stalled turn the handle in li...

Page 4: ...e system Models with activated carbon filter option certified for cyst reduction may be used on disinfected waters that may contain filterable cysts The UFC 100 UFC 207 UFC 209 and UFC 211 models All...

Page 5: ...ndard System with the exception of additional parts which must be installed as shown Additional parts include an Inlet Solenoid Valve Check Valve and External Prefilter Awater softener can be placed e...

Page 6: ...pre assembled System Base Base Controller Transformer 120VAC Stainless Steel Prefilter Two Stainless Steel Flex Hoses Inside the bubble bag 1 Drain Solenoid Valve Normally Closed 1 Nylon Elbow 2 Bras...

Page 7: ...ne diverted from the main water line is recommended to be installed upstream of the System for all exterior taps pool or hot tub makeup valves and irrigation systems This set up will help prolong the...

Page 8: ...The vertical spacing required is 36 from the bottom of the bracket If possible install the System at a height convenient for servicing Installation Drill into the concrete floor or block and anchor th...

Page 9: ...et up align the top mounting hole on the Bracket assembly with the pre drilled hole on the wall stud and secure the Bracket assembly with one 2 anchoring bolt Do not tighten this bolt completely 4b Th...

Page 10: ...to the local plumbing code in your area The directional arrow on the Inlet Solenoid Valve must point in the direction of the water flow Do not pressurize the Backpulse Tank to greater than 35psi Highe...

Page 11: ...all the Drain Solenoid Valve to the Brass Elbow using another Nipple 7b For UFC100 UF100 and UF100 with optional Surface Water Option Kit models connect the Drain Solenoid Valve normally closed to the...

Page 12: ...n in this manual to install the External Prefilter Connect the Stain less Steel Flex Hose on the Inlet Fitting assembly to the External Prefilter Once finished connect the External Prefilter to the MN...

Page 13: ...n the connection Take care not to cross thread this connection Fibre Chamber Air Vent Assembly 3 Complete Pre filter Chamber Air Vent Assembly as shown in FIGURE 24a A second Air Relief Valve is provi...

Page 14: ...A dedicated trap drain must be installed by a li censed plumber due to the complexity of venting sizing and trap installation Improper venting and trap installation can lead to sewer gases backing up...

Page 15: ...e Controller to the wall by tightening the two screws Use the plastic anchors if necessary 2 Ensure the transformer is not plugged into the electrical receptacle Connect the power supply cable from th...

Page 16: ...f power failure and will not activate the flushing and draining sequences NOTE Once the Controller is set the Controller will remember the Start Time Program Number and Flush Drain Interval settings i...

Page 17: ...ncrease frequency of flush drain cycle if the System TMP rises too quickly Increasing the number of Flush Drain cycles per day will prolong the life of the System however morewaterwillbeusedforsystemc...

Page 18: ...ing the Cap Wrench For models with a Stainless Steel Prefilter a Carbon Pre filter may be purchased separately if desired The Surface Water Option Kit is purchased separately from the System except fo...

Page 19: ...Controller Func tions section under E INSTALLATION INSTRUCTIONS on how to perform a Manual Flush sequence Following the Manual Flush open a cold water tap that is downstream of the System Allow water...

Page 20: ...e the flushing is complete open the Outlet Valve and a nearby COLD water tap to flush most of the chlorine from the System Run the tap fully open for at least 10 minutes Further flushing must be perfo...

Page 21: ...ity Tester into a power supply Press any button twice to turn it on Press the scroll keys until the screen displays Integrity Test Press ENTER and use the scroll keys to choose either Vertical or Hori...

Page 22: ...cause is a leak in the System from hoses connections or valves Be sure that all connections are tight before beginning the test and the Inlet and Outlet Valves are closed Leaky valves and loose connec...

Page 23: ...the System to protect your hands At the end of the procedure wash your hands thoroughly with soap and water Do not reuse the gloves Dispose of the gloves in the garbage Complete Paperwork The followi...

Page 24: ...Installation section under E INSTALLATION INSTRUCTIONS to install a new External Prefilter cartridge 4 Be careful to avoid MC1 cleaning agent coming in contact with skin or clothing Wash the mixing co...

Page 25: ...by installing a MNPT PVC plug H WINTERIZATION PROCEDURE 4 If an External Prefilter has been installed open the Mini Ball Valve on the bottom of the housing and allow to drain Press the red button on...

Page 26: ...Reinstall the plug into the Outlet Stainless Steel Flex Hose Fill with approximately 3 US gal 12litres of 58o F 50o C propylene glycol based plumbing antifreeze The UFC 207 UF 207 UFC 209 UF 209 UFC...

Page 27: ...nlet Valve and Outlet Valve Use the Controller to depressurize the System Use Pressure Gauges to ensure no pressure remains in the System Open Note If the winterization spring start up is combined wit...

Page 28: ...STALLATION INSTRUCTIONS initiate a manual flush and verify Drain Solenoid Valve is working Replace valve if necessary Water does not flow through System Black cap on Air Vent must be backed off by 1 5...

Page 29: ...heard from the Drain Solenoid Valve Replace valve if necessary Check connections are installed correctly and transformer is plugged in Inlet Solenoid Valve Doesn t close to allow System to drain On th...

Page 30: ...8 4 73 7 litres 7 5 19 5 gal 28 4 73 7 litres 7 5 19 5 gal 28 4 73 7 litres 7 5 19 5 gal 28 4 73 7 litres System efficiency 92 96 92 96 94 97 87 94 4 92 96 4 94 97 4 Controller voltage 24 VAC 24 VAC 2...

Page 31: ...litres 15 gal 56 7 litres Program 3 4 flush backpulse cycles 2 flush backpulse cycles 1 drain cycle 2 flush backpulse cycles 1 drain cycle Estimated water use US gallons 20 gal 75 6 litres 13 5 gal 5...

Page 32: ...re removed as the water passes from the outside of the Prefilter to the inside 2 The prefiltered water then passes down into the System to the membrane chamber 3 In the membrane chamber the water trav...

Page 33: ...he membrane and remain in your water This includes calcium and magnesium which contribute to your hard water and other dissolved solids like essential minerials and flouride How long does the automati...

Page 34: ...ressurize the System by turning on a tap until no water flows out from the tap 3 Drain the System by activating a Manual Flush sequence Refer to the instructions in the Controller Functions section un...

Page 35: ...bythehand 33 Reattach the Locking Clip Air Relief Valve Inlet Outlet Drain pipe assemblies Internal Prefilter System Cap External Prefilter if applicable and the Air Vent Assembly Reattach the Metal S...

Page 36: ...carefully remove and dispose of the Internal Prefilter D EXTERNAL PREFILTER REPLACEMENT Depending on the water quality the External Prefilter may need to be washed or replaced prior to the Annual Mai...

Page 37: ...37...

Page 38: ...UFC100 UF100 UF100 with Surface Water Option Kit Series 2 1 3 4 7 6 5 9 8 10 11 15 16 17 14 4 25 26 12 FIGURE 60 18 19 23 20 21 22 13 24 38...

Page 39: ...rvice Tag X X X 14 23029 Cap Wrench X X X Sub Assembly Kits 15 23117 Installation Sub Assembly Kit Inlet Pipe Assembly Kit Outlet Pipe Assembly Kit Drain Pipe Assembly Kit Air Relief Valve X X X 16 23...

Page 40: ...1 3 2 6 5 8 8 9 14 15 16 17 23 19 20 18 25 30 31 32 33 UFC 207 UF 207 UFC 209 UF 209 UFC 211 and UF 211 Series 21 24 FIGURE 61 11 10 22 27 26 28 29 7 4 40 13 12...

Page 41: ...153 System Cap Short X 15 23154 System Cap Long X 16 23214 Loading O ring X X 17 23260 Kit Locking Clip with mounting screw X X 18 23159 System Base X X 19 23172 Thimble Filter X X 20 23221 Plug 1 4 N...

Page 42: ...3060 Wall Bracket 8 23061 1 to Reducing Bushing 9 23183 Mini Ball Valve Plug 10 23062 Mini Ball Valve 11 23104 Housing Wrench External Prefilter Service Testing Kit Parts 12 23104 Housing Wrench Exter...

Page 43: ......

Reviews: