Acoustic Glass Break Detector

Installation Manual

A

PPLICATION

The GS930 is an acoustic glass break detector designed to detect break-
ing glass from framed windows in the perimeter of building. The detector
can safely and reliably detect glass breakage on both small and large ob-
jects as well as on single or multiple glazed objects.

I

NSTALLING

 

THE

 

DETECTOR

 

(

FIGS

1

 

TO

 

7)

Select a mounting position for the detector that is on a wall or ceiling adja-
cent to, or across from, the glass surface being monitored;

Only use for indoor installations;

Do not expose to any direct airflow;

Must have a line-of-sight view of all glass surfaces to be
protected;

Locate it no further than 8.5 m and not less than 1.0 m from the glass;

Mount it at least 0.15 m away from an adjacent wall or ceiling and at
least 1.8 m from the floor;

Can be temporarily mounted to conduct an initial functional test;

Must be permanently mounted on a stable and vibration-proof surface;

When closing the cover, ensure that the tamper contact spring is fed
into the recess in the cover.

"

In VDS-approved systems, the detector cover must be sealed with

an additional screw (enclosed with the detector) (Fig. 8).

S

PECIAL

 

NOTES

Do not mount the detector on the same wall as the glass surface being
protected.

If the glass is covered by inside shutters or sound deadening drapes,
or where exhibits or display items conceal the detector, check that the
detector is operating correctly before permanently mounting it (see
Functional testing during installation).

Do not use only one detector to protect glass in multiple rooms even if
the range test indicates the detector is operating correctly. This is a
precaution in case doors or other partitions are later placed between
the rooms.

Do not use in 24 hour-monitoring zones.

P

ROGRAMMING

 

(F

IG

. 6)

Power /status LED (Green)

Jumper J3

Off

Open

On

Closed

When closing the pins of jumper J3, the green LED remains lit when power
is applied to the detector. The green LED will extinguish for one second
when a loud sound occurs in the upper frequency rage, noting a pre-trip
condition. However, an alarm is not activated unless the other sound
characteristics required by 3 x 3 technology are also present.

Alarm LED (Red)

Jumper J4

RESET Input

Flashing for 2.5 sec

Open

Open

Latched after alarm

Closed

Open

Follows alarm relay

Closed

Permanently LOW

RESET

Closed

With LOW

When an alarm occurs, the red alarm LED flashes for 2.5 sec. When
latched, the LED will indicate a new alarm by flashing for 2.5 sec. and re-
latching afterwards. The latched LED can be reset by applying a LOW
signal to the RESET input.

F

UNCTIONAL

 

TESTING

 

DURING

 

INSTALLATION

 

(F

IGS

. 5 & 9)

High-frequency range testing:

Remove the detector cover;

Apply power and press the test button (SW2) once. The red and green
LEDs will start to quickly flash alternately. The detector is now ready for

high-frequency range testing;

Replace the detector cover;

Hold the tester near the surface of the glass to be protected and aim the
speaker at the detector from the furthest point of the glass. If there are
closed curtains, hold the tester behind them;

Slide the tester switch to TEST position, and a simulated glass break
sound will be produced every 10 seconds. If the glass is within range, the
flashing LED will latch for 2.5 sec. At the same time the alarm relay is
opened so that the appropriate detection line on the alarm control unit
will trip.

Low-frequency range testing:

To enter this mode while in the high-frequency test mode, press the
test button (SW2) a second time. The LEDs will now flash alternately at
a slower rate.

A sharp blow of the hand or other firm object to a framed hollow wall,
ceiling or door will cause the flashing LEDs to latch for 2.5 sec. and the
alarm relay to open.

IMPORTANT

: This test is not a range check.

The test mode lasts 5 minutes after which the detector automatically resets
to the normal operation mode. To manually exit the test mode, press the test
button until the LEDs stop flashing.

F

UNCTIONAL

 

TEST

 

IN

 

NORMAL

 

OPERATION

The detector must be in the normal operation mode with the cover in
place.

Hold the GT-2  tester directly against the glass surface to be protected
while aiming the loudspeaker towards the detector. Set the mode
selection switch to RUN.

Slap the glass to be protected with your flat hand. The unit automati-
cally produces a loud simulated glass break sound.

If the detector has been correctly installed, this should trigger an alarm.

S

PECIFICATIONS

Input voltage

9 to 15 VDC

- Max ripple

2 pp

- Voltage monitoring

6.4 V ± 0.4 V

Current consumption:
- Standby, no status LED

12 mA

- Standby, with status LED

14 mA

- Alarm, with alarm LED no status LED

9 mA

- Alarm, with latched alarm LED and status LED

15 mA

Alarm output:
- Semiconductor relay

opens on alarm

- Contact load rating

100 VDC / 120 mA

- Series resistance

35 ohm

Tamper contact

100 VDC / 500 mA

Sensitivity

automatic adjustment

Max. range

8.5 m radius

Area of the surface to be monitored

min 0.3 x 0.3 m, max 6 x 6m

Volume of the room to be monitored

min 22 m³, max 245 m³

Recommended glass thickness:
- Plate

3 mm to 6 mm

- Tempered

3 mm to 6 mm

- Wired

6 mm to 8 mm

- Laminated

6 mm to 8 mm

Environmental class II

-10 °C to +55 °C

EN

Summary of Contents for GS930

Page 1: ... 1 GS930 Acoustic Glass Break Detector Installation Manual NL DE FR EN DA SV NO ...

Page 2: ...shing for 2 5 sec and re latching afterwards The latched LED can be reset by applying a LOW signal to the RESET input FUNCTIONAL TESTING DURING INSTALLATION FIGS 5 9 High frequency range testing Remove the detector cover Apply power and press the test button SW2 once The red and green LEDs will start to quickly flash alternately The detector is now ready for high frequency range testing Replace th...

Page 3: ...d wechselt dann wieder auf Daueranzeige FUNKTIONSPRÜFUNG ABB 5 9 Hochfrequenzbereichs Prüfungsmodus Nehmen Sie die Abdeckung des Melders ab Legen Sie Spannung an und betätigen Sie den Prüf Taster SW2 einmal Das schnelle abwechselnde Blinken der roten und grünen LED zeigt den Hochfrequenzbereichs Prüfungsmodus an Bringen Sie die Abdeckung wieder am Melder an Plazieren Sie den Glasbruchsimulator Han...

Page 4: ...reste allumée fixe La LED déclenchée peut être réinitialisée en appliquant un signal bas 0 volt sur l entrée Reset ou en appuyant sur le bouton de test SW2 trois fois TEST FONCTIONNEL LORS DE L INSTALLATION FIG 5 ET 9 Test de la portée haute fréquence Retirez le boîtier du détecteur Mettez sous tension et appuyez sur le bouton de test SW2 une fois Les LED rouge et verte commencent à clignoter rapi...

Page 5: ...n nieuwe alarmsituatie door 2 5 seconde te knipperen en zich vervolgens opnieuw te vergrendelen De vergrendelde LED kan worden gereset door een LAAG signaal te sturen naar de RESET ingang of door testknop SW2 driemaal in te drukken NL FUNCTIONELE TEST TIJDENS INSTALLATIE FIG 5 EN 9 Test van hoge frequentiebereik Open de kap van de detector Schakel de spanning in en druk de testknop SW2 eenmaal in ...

Page 6: ...en LÅG signal på ingången RESET eller trycker på testknappen SW2 tre gånger FUNKTIONSTEST VID INSTALLATION BILD 5 OCH 9 Test av högfrekvensintervallet Ta bort locket på detektorn Anslut strömmen och tryck på testknappen SW2 en gång Röd och grön LED börjar blinka snabbt växelvis Detektorn är nu klar för test av högfrekvensintervallet Montera locket Håll testapparaten nära glasytan som ska övervakas...

Page 7: ...kommelsen kan resettes med et O volt signal på RESET indgangen FUNKTIONSTEST UNDER INSTALLATION FIG 5 9 Høj frekvens rækkevidde test Aftag detektorlåget Tilslut forsyningsspænding og tryk én gang på testknappen SW2 Den røde og den grønne lysdiode begynder at blinke hurtigt skiftevis hvilket viser at detektoren er klar til høj frekvens rækkevidde test Påsæt detektorlåget Hold glasbrudstesteren type...

Page 8: ...arm ved å blinke i 2 5 sekunder før ny indikering En latchet LED kan tilbakestilles enten ved å tilføre et LAV signal til RESET inngangen eller ved å trykke tre ganger på SW2 testknappen FUNKSJONSTESTING UNDER INSTALLERING FIGUR 5 OG 9 Høyfrekvent rekkeviddetesting Ta av detektorlokket Tilfør strøm og trykk én gang på testknappen SW2 Den røde og grønne LEDen vil begynne å blinke raskt vekselvis De...

Reviews: