I
NSTALLATION
OI 250 (EN)
REV7
/REV7
6.5.3
Aligning the Lattice Supports
• Using a water level or hydrostatic level, align the lattice supports
(1) with one another at the same height and in the longitudinal
and transverse directions by adjusting the nuts (2) on the anchor
bolts (4). Use the upper surfaces of the lattice supports (mounting
surfaces for pole column) as the reference surface. Tighten the
nuts to a torque of 250 Nm and lock them.
1
Lattice support 1x
2
Nut, M24
12x
3
Washer, 24
8x
4
Anchor bolts
Provided at site by customer (corrosion-
resistant steel with minimum strength of
Rp 235N/mm²)
5
Foundation
Provided at site by customer
6
Lifting tackle
-
6
1
5
4
3
2
BA-
P-G
ITT
ER
-G
S-H
E
BE
N