Chapter 4 Detailed Descriptions of the Fieldbus Network Adapters
GFK-2958E
RSTi-EP User Manual
88
4.4.6
0x1000
–
0x1006 Network adapter Identifier
The identifier is the product designation: EPXMBE001 and EPXMBE101 as per Network adaptor
catalogue number.
4.4.7
0x1000
–
0x1006 Network adapter Status
Bit
Name
Meaning
0
Summarized module diagnosis A diagnosis is available on at least one module with diagnostics functionality.
1
Errorbit 1
Reserve bit 1, currently not used
2
Errorbit 2
Reserve bit 2, currently not used
3
Systembus error
Error on system bus. Communication with the connected modules is disrupted.
4
Errorbit 4
Reserve bit 4, currently not used
5
Errorbit 5
Reserve bit 5, currently not used
6
I/O-Configuration error
Differing configuration. The module list has changed. The list of configured
modules (reference module list 0x2800
–
0x287F) differs from the module list
detected by the network adapter (current module list 0x2A00
–
0x2A7F).
7
Master configuration error
Master configuration error. The list of configured modules (reference module list
0x2800
–
0x287F) differs significantly from the module list detected by the
network adapter (current module list 0x2A00
–
0x2A7F). Process data cannot be
exchanged with the modules.
8
Errorbit 8
Reserve bit 8, currently not used
9
Errorbit 9
Reserve bit 9, currently not used
10
Force mode active
Force mode was activated via the web server. Forced channels do not exchange
data with the master.
11
Errorbit 11
Reserve bit 11, currently not used
12
Errorbit 12
Reserve bit 12, currently not used
13
Voltage U
OUT
error
Error in the supply voltage of outputs
14
Voltage U
IN
error
Error in the supply voltage of system and inputs
15
Errorbit 15
Reserve bit 15, currently not used
4.4.8
0x1010 Process Image Length in Bits for the Output Modules
4.4.9
0x1010 Process Image Length in Bits for the Input Modules
4.4.10
0x1017 Register
–
Mapping Revision
Version of the register structure
4.4.11
0x1018
–
0x101B Collective Diagnostics Message for I/O Modules
If a diagnostic alarm is activated (register 0x1134) and there is a diagnostic message for a module, it
is indicated here with a set bit. A module’s slot position corresponds to its position in the 64
-bit data
field (minus passive modules without slot recognition). Example: 0x0000 0000 0000 0002 = There is a
diagnostic alarm for module 2.
Reading
the module’s diagnostic memory (0xAXXX) confirms
the diagnosis and resets the
corresponding bit. In case of multiple diagnoses for one module, only the most up-to-date diagnosis
is displayed. The next diagnostic is then placed in a wait loop and only becomes active once the
current one has been confirmed.
Summary of Contents for GFK-2958E
Page 1: ...RSTi EP User Manual GFK 2958E November 2017 ...
Page 23: ...Chapter 1 Introduction GFK 2958E RSTi EP User Manual 19 Notes ...
Page 56: ...Chapter 3 Configuration GFK 2958E RSTi EP User Manual 52 Notes ...
Page 183: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 179 EP 5111 ...
Page 184: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 180 EP 5111 ...
Page 316: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 312 Notes ...
Page 330: ...Chapter 6 Installation GFK 2958E RSTi EP User Manual 326 Notes ...
Page 344: ...Chapter 7 Earthing and Shielding GFK 2958E RSTi EP User Manual 340 ...
Page 345: ...Chapter 7 Earthing and Shielding GFK 2958E RSTi EP User Manual 341 Notes ...
Page 385: ...Chapter 8 Web Server GFK 2958E RSTi EP User Manual 381 Notes ...
Page 401: ...Chapter 11 Disassembly and Disposal GFK 2958E RSTi EP User Manual 397 Notes ...
Page 413: ...Chapter 12 LED Indicators and Troubleshooting GFK 2958E RSTi EP User Manual 409 Notes ...
Page 416: ...Chapter 14Accessories and Replacement Parts GFK 2958E RSTi EP User Manual 412 Notes ...