FVP 110 Fieldbus Valve Positioner Manual
200
GE Energy
18
5018
SP_RATE_
DN
+INF
Rate-of-decrease limit for SP effective in
AUTO, CAS, and RCAS modes. If this
parameter is 0, no limit is applied to the rate of
decrease.
19
5019
SP_RATE_
UP
+INF
Rate-of-increase limit for SP effective in AUTO,
CAS, and RCAS modes. If this parameter is 0,
no limit is applied to the rate of increase.
20
5020
SP_HI_LIM
100
Upper limit for setpoint (SP)
21
5021
SP_LO_LIM
0
Lower limit for setpoint (SP)
22
5022
CHANNEL
1
O/S
Defines the channel number of the
hardware channel connected to the
transducer block. Always set to 1 for the
AO block in a FVP110.
23
5023
FSTATE_
TIME
0 second
Defines the time from when the fault state
of the RCAS_IN or CAS_IN is detected to
when the output should be set to the level
preset in FSTATE_VAL (this action takes
place only if Fault State to value is set as
true in I/O_OPTS).
24
5024
FSTATE_VAL
0
Preset output level for fault state. See
above.
25
5025
BKCAL_OUT
–
—
Value to be input to BKCAL_IN of the
downstream block; used by the
downstream block to prevent reset windup
and perform bumpless transfer to
closed-loop control.
26
5026
RCAS_IN
–
Remote cascade setpoint set by the host
computer, etc.
27
5027
SHED_OPT
1
Defines the mode shedding action to be
taken upon occurrence of time-out of
communication in a mode using the
remote setpoint.
28
5028
RCAS_OUT
–
—
Remote setpoint sent to a host computer,
etc.
Table 62
AO Block Parameters (Continued)
Relative
Index
Index
Parameter
Name
Default
(factory
setting)
Write
Description
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......