FVP 110 Fieldbus Valve Positioner Manual
180
GE Energy
Valve responses are too
slow.
If only the responses that
require air suction are slow, it
means that the regulator’s
maximum capacity is large
enough.
Replace the regulator.
—
The I/P module’s nozzle has
become blocked from dirt
contained in the air supply or
the like.
Check whether or not error
114 or 122 occurs in
XD_ERROR in steady
states. If it does occur,
contact the nearest
service station or
representative office.
The control relay’s nozzle has
become blocked from dirt
contained in the air supply or
the like.
Check whether or not error
114 or 122 occurs in
XD_ERROR in steady
states.
The control gain is insufficient. Write 4 or 3 to
AUTO_TUNE_EXEC to
redo auto tuning. Or,
increase the
SERVO_GAIN setting.
❑
“Carrying out
Tuning” on
page 61
❑
“Control
Parameters”
on page 132
❑
“Function
Block Parame-
ters” on
page 183
❑
“Manual Tun-
ing Guideline”
on page 253
There’s air leak from the pipe
of output pressure, or
feedback lever is not correctly
attached.
Check the piping and
attachment of the lever,
and write 4 or 3 to
AUTO_TUNE_EXEC to
redo autotuning.
❑
“Installing the
FVP110 on the
Actuator” on
page 35
❑
“Carrying out
Tuning” on
page 615.3
The pressure balance
deviation is too large.
Adjust the pressure
balance of control relay.
“Tuning the
Pressure Balance
of Control Relay”
on page 71
Table 57
Troubleshooting Valve Control (Continued)
Problem
Presumed Cause
Remedy
See Section
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......