2. OPERATION PRINCIPLES
GEK-106305A
DTR Digital Tap Changer Controller
19
AUTOMATIC
This signal shows the operation mode of the regulation automatism, and it can be either Automatic or Manual.
REMOTE
This signal shows the mode of the OLTC, either Remote or Local.
|DV| > ID
This signal becomes active when the absolute value of the difference between the measured voltage (real voltage)
and the setpoint is greater than the Insensitivity Degree, and therefore the DTR system has to start an operation on
the OLTC.
QUICK LOWERING
This signal becomes active when the measured voltage is greater than the
Quick Lowering
setting and, therefore,
the regulation automatism (in automatic mode) will perform a tap decrease without waiting the operating time.
OVERVOLTAGE
This signal becomes active when the measured voltage is greater than the OVERVOLTAGE setting and, therefore,
the regulation automatism (in automatic mode) will not operate.
UNDERVOLTAGE
This signal becomes active when the measured voltage is lower than the UNDERVOLTAGE setting and, therefore,
the regulation automatism (in automatic mode) will not operate.
OVERCURRENT
This signal becomes active when the measured current is greater than the OVERCURRENT setting and, therefore,
the regulation automatism (in automatic mode) will not operate.
REM TRIP COMMAND
This signal indicates that the unit has Received a Remote Trip Command via communications
STOP COMMAND
This signal becomes active when the DTR receives by communications a command to stop the regulation
automatism.
AUTOMATIC COMMAND
This signal becomes active when the DTR receives by communications a command to change the regulation
automatism to AUTOMATIC mode.
MANUAL COMMAND
This signal becomes active when the DTR receives by communications a command to change the regulation
automatism to manual mode.
Summary of Contents for DTR GEK-106305A
Page 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Page 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Page 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Page 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Page 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Page 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Page 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Page 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Page 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Page 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...