2. OPERATION PRINCIPLES
8
DTR Digital Tap Changer Controller
GE—106305A
The Operation Time to initiate a tap change will be calculated in the following way:
Tb = 10 * ID / |DV|
tb==Base Time
OT = FT * tb
The user can set the Time Factor (FT) and
DV
is the deviation between the real voltage and the setpoint
calculated in the following way (depending on the selected algorithm)
Algorithm 1: Voltage regulation:
DV = V
0
- V
m
V
0
: setpoint, V
m
: Measured voltage
Algorithm 2: Compensating by means of the calculation of apparent current:
DV = (V
0
+ V
com
) - V
m
V
0
=setpoint, V
m
= Measured voltage
V
com
= K
com
* I
m
/ I
n
K
com
==Calculation of current (Adjustable)
I
m
=Measured current, I
n
=Nominal current
Only when
V
com
< V
comax
Otherwise
V
com
= V
comax
V
comax
==Maximum voltage increase (Adjustable).
Summary of Contents for DTR GEK-106305A
Page 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Page 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Page 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Page 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Page 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Page 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Page 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Page 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Page 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Page 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...