4. PROGRAMMING THE UNIT
46
DTR Digital Tap Changer Controller
GE—106305A
If the operation is performed correctly, the relay will show the following message:
OPERATION
PERFORMED
4.5 ALARMS SCREEN
If we move from the main screen to the alarms screen, by pressing F1, as shown on the main screen graphic, the
relay will show a new screen, as the one below:
This screen shows a list of alarms that have been generated in the substation. The maximum number of alarms that
can be displayed is 12. Alarms are displayed as follows:
Alarm label, that is, associated text defined in GE-INTRO software
Time and date when the alarm was generated
When an alarm is produced, the screen shows the previous information with a dark shadow and blinking. The blink
and the shadow indicate that the alarm has not been acknowledged. In order to “acknowledge” the alarm, we must
press F2, as indicated in the help text shown at the bottom of the screen. Once the alarm has been acknowledged, it
stops blinking and the shadow disappears, but the alarm text remains on the screen until the reason that produced it
disappears.
At the bottom of the screen we can see the text “ACTIVE ALARM, NOT ACKNOWLEDGED”, “ACTIVE ALARM”, etc.
showing the status for each alarm.
The representation for the different possible statuses of an alarm are as follows:
Active alarm, not acknowledged:
Blinking, with a dark shadow, and marked with an asterisk
Active alarm, acknowledged:
Without blinking, marked with an asterisk.
Inactive alarm, not acknowledged:
Without blinking, with a dark shadow, without asterisk.
Inactive alarm, acknowledged:
Disappears from the screen.
Summary of Contents for DTR GEK-106305A
Page 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Page 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Page 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Page 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Page 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Page 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Page 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Page 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Page 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Page 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...