7. ACCEPTANCE TESTS
68
DTR Digital Tap Changer Controller
GE—106305A
7.9.2 VERIFICATION OF THE NUMBER OF “SUCCESSIVE OPERATIONS”
Set the relay as follows
GENERAL SETTINGS:
Nº OPERATIONS
0
Nº SUCCESSIVE OPERATIONS
4
TIME
WINDOW
1 min.
COUNTERS:
Nº OPERATIONS
0
Verify that after finishing the following sequence, S15 (SUCCESSIVE OPERATIONS) is activated.
Before initiating the sequence, apply a zero to inputs E1, E2, E3, E4, E5, E6
1. Activate E1 .
(The relay will show that it is on Tap 1)
2. Apply a pulse to
“TAP-UP”
and wait for S1 to activate.
3. Deactivate E1 and activate E2
(Move from Tap 1 to Tap 2).
4. Apply a pulse to
“TAP-UP”
and wait for S1 to activate.
5. Activate E1 .
(Move from Tap 2 to Tap 3).
6. Apply a pulse to
“TAP-UP”
and wait for S1 to activate.
7. Deactivate E1 and E2, and activate E3.
(Move from Tap 3 to Tap 4)
8. Apply a pulse to
“TAP-UP”
and wait for S1 to activate.
9. Activate E1 .
(Move from Tap 4 to Tap 5)
10. Apply a pulse to “
TAP-UP
” and check that S15 activates
With the previous settings, set the COUNTERS and No OPERATIONS settings to 0, and after the following
sequence, check that S15 doesn’t activate, and that the number of operations when finishing the sequence remains
at 0.
1. Activate
E1.
2. Apply a pulse to
“TAP-UP”
and wait for 20 s.
3. Deactivate E1 and E2, and activate E3.
4. Apply a pulse to
“TAP-UP”
and wait for 20s.
5. Activate E1 .
6. Apply a pulse to
“TAP-UP”
and wait for 20 s.
7. Deactivate E1 and E2, and activate E3
8. Apply a pulse to
“TAP-UP”
and wait for 20s.
9. Activate
E1.
10. Apply a pulse to
“TAP-UP”
; S15 should not operate.
Summary of Contents for DTR GEK-106305A
Page 5: ...TABLE OF CONTENTS 4 DTR Digital Tap Changer Controller GE 106305A ...
Page 49: ...4 PROGRAMMING THE UNIT 48 DTR Digital Tap Changer Controller GE 106305A ...
Page 55: ...5 TECHNICAL CHARACTERISTICS 54 DTR Digital Tap Changer Controller GE 106305A ...
Page 71: ...8 INSTALLATION AND MAINTENANCE 70 DTR Digital Tap Changer Controller GE 106305A ...
Page 83: ...9 KEYPAD AND DISPLAY 82 DTR Digital Tap Changer Controller GE 106305A ...
Page 87: ...FIGURES 86 DTR Digital Tap Changer Controller GE 106305A FIGURE 3 PANEL MOUNTING DIAGRAM ...
Page 88: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 87 FIGURE 4 RS 232 CONNECTION ...
Page 89: ...FIGURES 88 DTR Digital Tap Changer Controller GE 106305A FIGURE 5 DIMENSIONS DIAGRAM ...
Page 90: ...FIGURES GEK 106305A DTR Digital Tap Changer Controller 89 FIGURE 6 FRONT VIEW ...
Page 91: ...FIGURES 90 DTR Digital Tap Changer Controller GE 106305A FIGURE 8 GENERIC REAR VIEW ...