Operatine Manual
SitePro 60 kVA
8.1.2 Start-up procedure after maintenance shut down.
NOTE !
UPS system has been turned
OFF
following the maintenance shut down procedure
and the load is still powered by the maintenance switches
Q2
.
The load must be transferred back to the UPS system
.
Open the front door and make sure that:
a)
The
safety screens
are fixed in their position.
b)
The
switches
Q1
and
Q4
are OFF
(0) and the external
battery circuit breaker or battery fuses are
open
. The
switch Q2
must be closed.
c)
The electronic power supply and the control panel are ON.
LEDs 2, 8, 9, “alarm”
and
“service
check”
are
ON.
The
LCD panel
(main screen) must indicate the status
“load off”
.
FOR THE SINGLE VERSION PERFORM THE FOLLOWING OPERATIONS
1. If not already supplied (separate mains inputs), switch-ON the mains power to the rectifier input.
2. Close the input switch Q4.
LED 1
must be lighted and
LED 3
(inside rectifier symbol) must blink.
The rectifier starts up automatically, supplying the DC circuit, and charging the DC capacitors.
After some seconds, the
contactor K3
closes (the green
LED 1 - K3 ON
on
“P1 - Power Interface”
lights
up, see
Fig. 4.8.2-1
).
The
LED 3
(inside rectifier symbol) stops blinking and stay ON, indicating that the DC link has reached
the floating voltage.
3. Battery coupling to DC link.
Close the external battery circuit breaker or battery fuses, after checking the right polarity.
The
battery
is now connected to the DC link.
LED 4b
should be lit indicating battery charge.
The
buzzer
switch OFF and LED
“alarm”
is OFF.
4.
Close the output switch Q1.
The load is now supplied by the mains through both the automatic and manual bypass.
The LCD panel (main screen) must indicate the status
“LOAD ON BYPASS”
.
LED 2, 7,8
and
9
is ON and
"service check"
is OFF.
(In case the
"load off"
has been previously activated, a reset is needed to enable the bypass).
5.
Now open the maintenance switch Q2.
LED 9 is OFF.
The load is now supplied only through the electronic bypass.
The control panel should now indicate a normal situation (No alarms).
LED 1, 2, 3, 4b, 7
and
8
are ON.
LED 4a, 5, 6
and
9
are OFF.
LED
“Service check”
is OFF.
6.
Inverter start.
Press the key
"I"
on the control panel.
The
inverter
will start up.
LED 5
(inside inverter symbol) blinks.
In a short time, when the inverter voltage is confirmed, the LED stops blinking and stays continuously
lit. The
load
will be automatically transferred from mains to
inverter
.
LEDs 1, 2, 3, 4b, 5, 6
and
8
are now lit.
LEDs 4a, 7
and
9
are OFF.
The LCD panel must display the main screen, indicating the status
“LOAD ON INVERTER”
and the
value of the battery reserve.