Operatine Manual
SitePro 60 kVA
The UPS cabinet is free standing and normally does not require bolting to the floor.
In any case the cabinet basement is suitable to be floor fixed, when requested by local standards.
In case of parallel system, try to place the UPS
modules in sequence of their numbers (marked
on the packing).
If the units are positioned “
side by side
”, the side
panels must be mounted on all units.
Remove the side air inlet grids on the
intermediate units to run the control bus cable
connections.
Fig. 4.4.1-3 RPA system disposition
4.4.2 Battery
location
Batteries require a well-ventilated room with controlled temperature to obtain reliable operation.
The
Battery
can be install immediately adjacent to the UPS (left or right side) or remotely from the UPS.
If the
Battery
is installed remotely from the UPS, a wall mounted DC disconnect device must be installed
within line-of-site to both the UPS and the
Battery
.
The optimal room temperature for the
Battery
is 20°C (68°F) to 25°C (77°F).
The life of valve-regulated batteries will be reduced by 50% for each additional
10°C
(18°F) that the
Battery
ambient temperature is above
25°C
(77°F).
The
Battery System
associated with larger UPS is usually either rack mounted or installed in multiple
Battery Cabinets
.
Installation and assembly must be made according to the local standards and
Battery System
manufacturer‘s recommendations.
The
Battery Circuit Breaker
or
Battery Fuse Box
must be mounted as near as possible to the
Battery
.
WARNING !
Battery installation and connection must be performed by QUALIFIED PERSONNEL
ONLY.
Read all
safety instructions
before proceeding with the installation (see
Section 1)
.