Operatine Manual
SitePro 60 kVA
7.1 METERING
MODE
The Metering mode is entered any time the
metering
button is pressed.
While in this mode the LCD will display a series of screens containing metering information.
In this mode the buttons perform the following functions:
metering
scrolls forward to the next screen.
alarms
abandons the Metering mode and enters the Alarms mode.
parameters
abandons the Metering mode and enters the Parameters mode.
+
scrolls forward to the next screen.
–
scrolls backward to the previous screen.
ok
displays the main screen for this mode.
Main screen
This screen displays the current status of the UPS in a condensed form.
The information offered by this screen consists of:
•
The type of the machine: family name, series number (P + unit number for parallel version from 1 to
8) and power range.
•
The status of the load (referred to the most loaded phase - for RPA: respect to the rated power of
Parallel System).
•
The estimated battery backup time in minutes with the present load.
SitePro S7 60kVA
LOAD ON INVERTER
LOAD = 50%
Autonomie = 12min
metering
alarms
parameters
+
–
ok
Battery data screen
This screen displays:
•
The battery voltage.
•
The battery current (negative values correspond to the discharge of the battery).
•
The temperature of the battery (XXX indicates sensor disabled).
•
The current charge level.
•
The estimated backup time with the present load.
Ub=408V Ib=
5A
Battery Temp = + 25
°
C
Charge Level = 50%
Autonomy =
12min
metering
alarms
parameters
+
–