g
GE
OPM_LPS_31E_8K0_20K_1GB_V010.doc
26/40
Operating
Manual
LP 31
/ 8-10-15-20
kVA
4.3.4 Setup menu
To enter the setup menu:
1- Be sure the UPS is
switched OFF.
2- Press push-button “
enter/reset
“ (front panel) and
simultaneously
turn switch “UPS
ON/OFF“ (front panel) into position “ON“ (up).
Using push-buttons “+” and “-” you can scroll through the several setup screens, “
enter/reset
“
confirms a screen choice.
After selecting a setup screen you can scroll through its settings using the push-buttons “+”
and “-”, a setting is confirmed by pressing “enter/reset“.
To abort the setup procedure (i.e. without changing the setting) just wait the 20 seconds
time-out period after which the default screen will return.
SETUP SCREENS
ENTER/RESET exit
The intro setup screen.
“enter/reset” return to the default screen.
You can also wait 20 seconds: the time-out period of no key
activity.
Pressing “+” display the screens in the following order:
WARNING: OUTPUT
CHANGE ON LINE
A short reminder that the new settings will be valid
immediately after pressing the
“enter/reset”
key.
LANGUAGE
ENGLISH
Changes the language of the screen messages:
you can select: English, German, French, Italian and
Spanish.
OUTPUT FREQUENCY
50.0Hz
The system output frequency. Range: 50/60 Hz.
CAUTION !
Changing of the output frequency can cause
severe damage of equipment connected to
the UPS:
Be sure that the new frequency is suitable for
the connected equipment.
FREQUENCY RANGE
2%
The frequency tracking range (in which the output converter
frequency will follow the bypass frequency).
Range: 2/4/6 %.
If the bypass frequency is beyond the setting, the output
converter will return to the fixed crystal controlled frequency.
PLL LOCK SPEED
NORMAL
The frequency tracking speed range (in which the output
converter frequency will follow the bypass frequency).
Range: NORMAL (1Hz/sec), HIGH (5Hz/sec).