Operating
Manual
LP 31
/ 8-10-15-20
kVA
18. In order to calculate the available back-up time related to the actual load, information on the
capacity of the battery set is stored in the UPS.
As the total battery capacity changes when battery extension packs are installed, the battery
capacity must be re-programmed.
Please contact your dealer.
19. An emergency shutdown device can be connected to connector 18 on the interface PCB, pin 14
and pin 15.
Off factory the pins 14-15 are interconnected.
For more information see chapter 4.3.
20. For advanced communication possibilities, the ComConnect interface port (9-pin connector at
the rear of the unit) can be connected to a computer system (RS232 protocol). Furthermore four
potential free contacts are available.
21. A plug-in UPS network interface card (optional) makes the UPS “SNMP manageable”.
This option can be used to connect the UPS directly to a computer network.
See chapter 5 for more information.
22. If you have not installed a battery pack install all battery fuses at the front. Start at the upper
side. The number of fuses shipped with the UPS depends on the rating of the UPS:
LP 31
/ 8 - 10 kVA
= 4 fuses
LP 31
/ 15 - 20 kVA
= 8 fuses
23. Reinstall the rear panel and the lower front panel.
24. Connect the mains power to the UPS.
25. Turn all MCBs (ON/OFF, mains, bypass) into “ON” position (the sequence is not important).
Note: the UPS can be started on battery power when the mains input voltage is not available:
just switch the UPS on with the ON/OFF switch.
To prevent accidental discharging of the batteries, it is recommended to start the unit
only when the mains input voltage is available.
26. Reinstall the middle front panel.