QUICK BATTERY
TEST PRESS ENTER
Start of the manual Quick Battery Test.
See for more information chapter 4.4.2 “
Quick Battery Test”
.
CALIBRATE BAT
Press DOWN+ENTER
Start of the manual Deep Battery Calibration Test.
See for more information chapter 4.4.3 “
Deep Battery
Calibration Test
”.
IC: I1h1
+ 5.7A
-5.9A
Service information on internal UPS components.
BYPASS OK
BYPASS off
Service information on internal UPS components.
LAST TEST TIME
10:17:15 14.0Ah
Duration of latest test performed, hh/mm/ss,
(hours/minutes/seconds).
FORCE BYPASS
press DOWN+ENTER
The UPS transfers the load to bypass when the keys “-” (2)
and “
enter/reset
” (3) on the front panel are depressed
simultaneously during approx. 2 seconds.
If the bypass supply is not within limits, the lower line will show
the text “UNAVAILABLE”.
AUTOMATIC BYPASS
ENABLED
Service set up information whether the bypass is enabled
(default) or disabled. If disabled: UPS will NOT go to bypass.
BATTERY 14Ah
BAT. CHARGE 99%
Service set up information about the total battery capacity.
Information about the actual battery charge condition.
PLL LOCK SPEED
NORMAL
Service set up information about frequency tracking speed for
the inverter to follow the bypass frequency, NORMAL
(1Hz/sec.) is the normal value and default.
HIGH (5Hz/sec.) may be suitable if the UPS is connected to a
generator with fast frequency changes and the UPS must be
synchronised to prevent alarms.