background image

0.004  Amp 
0.004  Amp 

60 
50 

GEK-65525 

TABLE  II 

0.27  0.62  0.68 
0.23  0.52  0.57 

Watts 

6.8 
5.9 

Vars 

15.6 
13.0 

Vo ltAmperes 

17.0 

14.3 

The  potential  burdens  at  rated  voltage  and  rated  frequency  are  given  in  Table  III. 

TABLE  II I 

Volts 

Watts 

Vars 

60 

115 

408 

710 

815 

8.1 

14.1 

16.2 

60 

208 

1350  2300  2640 

8.4 

14.3 

16.4 

50 

115 

413 

720 

830 

8.0 

13.9 

16.0 

50 

208 

1370  2370  2730 

7.9 

13.7 

15.8 

CHARACTERISTICS 

This  relay  consists  of  three  single-phase  directional  units  with  the  three  rotors  on 
a  common  shaft. 

Each  unit  develops  maximum  torque  when  the  current,  through  the 

current  coils,  leads  the  voltage,  applied  to  the  potential  coils,  by  30o. 

When  the 

delta  voltages  are  applied  to  the  potential  coils,  as  shown  in  Figure  2,  the 

currents  in  the  current  coils  will  lead  these  voltages  by  300  when  the  three-phase 

system  is  at  unity  power  factor. 

For  example,  the  top  unit  is  connected  so  that  it 

will  have  Phase  1  current  in  its  current  coils  (studs  3-4)  and  Phase  1-3  on  its 

potential  coils  (studs  13-14). 

The  relay  will  therefore  respond  to  the  watt 

component  of  the  power  (Figure  7). 

The  High-Seismic  target  and  seal-in  unit  has  two  tap  selections  located  on  the  front 

of  the  unit.  See  Figure  8. 

RECEIVING,  HANDLING  AND  STORAGE 

These  relays,  when  not  included  as  part  of  a  control  panel,  will  be  shipped  in 

cartons  designed  to  protect  them  against  damage. 

Immediately  upon  receipt  of  a 

relay,  examine  it  for  any  damage  sustained  in  transit. 

If  injury  or  damage 

resulting  from  rough  handling  is  evident,  file  a  damage  claim  at  once  with  the 
transportation  company  and  promptly  notify  the  nearest  General  Electric  Sales 

Office. 

Reasonable  care  should  be  exercised  in  unpacking  the  relay  in  order  that  none  of  the 

parts  are  injured  nor  the  adjustments  disturbed. 

If  the  relays  are  not  to  be  installed  immediately,  they  should  be  stored  in  their 
original  cartons  in  a  place  that  is  free  from  moisture,  dust  and  metallic  chips. 

Foreign  matter  collected  on  the  outside  of  the  case  may  find  its  way  inside  when  the 

cover  is  removed,  and  cause  trouble  in  the  operation  of  the  relay. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for CCP13E

Page 1: ...INSTRUCTIONS THREE PHASE POWER DIRECTIONAL RELAY TYPE CCP13E GEK 655258 GE Meter and Control 205 Great Valley Parkway Malvern PA 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ...UNIT INSTALLATION PICKUP HIGH SEISMIC TARGET AND SEAL IN UNIT PERIODIC CHECKS AND ROUTINE MAINTENANCE PICKUP HIGH SEISMIC TARGET AND SEAL IN UNIT SERVICING RELAY CONTACTS BEARINGS V0LTAGE BIAS POLARITY ANGLE OF MAXIMUM TORQUE PICKUP ADJUSTMENT CLUTCH ADJUSTMENT HIGH SEISMIC TARGET AND SEAL IN UNIT RENEWAL PARTS LIST OF ILLUSTRATIONS PAGE 3 3 4 5 6 6 7 7 8 8 8 9 9 9 10 10 11 11 11 11 11 11 11 12 13...

Page 3: ...re 1 with normal load flow from the system to the load If a single phase to ground fault were to occur at F it would be cleared at source 2 but not necessarily at breaker 2 because of delta wye transformer 2 However it is desirable to open circuit breaker 2 to clear the ground fault completely This can be accomplished by the CCP13E relay associated with circuit breaker 2 The CCP13E is generally se...

Page 4: ...e applied voltage Thus the minimum pickup in this case will be the nameplate value divided by 0 95 and the 0 004 ampere relay will have a minimum pickup at 95 voltage of 0 004 0 95 0 0042 Secondary Amperes Based on the maximum full load current the smallest CT ratio that could be used is 500 5 With this ratio the core loss component of current would be 0 i 7 o oo567 s d A econ ary mperes Since the...

Page 5: ...ws holds the connecting plugs in place The relay case is suitable for either semiflush or to two inches thick and appropriate hardware thickness must be indicated on the relay order to be included surface mounting on all panels up is available However panel insure that proper hardware will These relays are induction cylinder devices for alternating current AC circuits The principle by which torque...

Page 6: ...ertz relay is available with potential coils rated for 115 or 208 volts The current coils of all models are rated 5 amperes continuously or 200 amperes for 1 second The relay has maximum torque when the three phase system is a unit power factor if the relay is connected as shown in Figure 2 The balanced three phase current to operate the relay at maximum torque angle and with rated voltage on the ...

Page 7: ...s studs 3 4 and Phase 1 3 on its potential coils studs 13 14 The relay will therefore respond to the watt component of the power Figure 7 The High Seismic target and seal in unit has two tap selections located on the front of the unit See Figure 8 RECEIVING HANDLING AND STORAGE These relays when not included as part of a control panel will be shipped in cartons designed to protect them against dam...

Page 8: ...cal end play of the moving contact and shaft assembly It should be between 1 64 inch and 1 32 inch 6 The contact gap should be approximately 3 64 inch 7 The contact wipe should be 0 004 inch to 0 009 inch If there is reason to believe that the jewel is cracked or dirty the screw assembly can be removed from the bottom of the unit and examined under a microscope or the surface of the jewel explored...

Page 9: ...and or voltage The purity of the sine wave i e its freedom from harmonics cannot be expressed as a finite number for any particular relay however any relay using tuned circuits RL or RC networks or saturating electromagnets such as time overcurrent relays would be essentially affected by non sinusoidal waveforms DIRECTIONAL UNITS Polarity Complete polarity tests are made at the factory but these m...

Page 10: ...inals 1 and 11 to a DC source using a load box to control the current over a range of 0 1 to 2 amperes 2 Close the left contact manually 3 Increase the current slowly until the seal in unit picks up See Table IV The target must latch in 4 Decrease the current slowly until the seal in unit drops out See Table IV The target must remain latched in Reset the target before checking pickup again TAP 0 2...

Page 11: ...rience to select the test interval best suited to his individual requirements it is suggested that the points listed under ACCEPTANCE TESTS be checked at an interval of from one to two years These tests are intended to make sure that the relays have not deviated from their original settings If deviations are encountered the relay must be retested and serviced as described in this manual PICKUP Per...

Page 12: ... left hand contact barrel 1 revolutions 5400 and tighten its clamping screw To change the stationary contact mounting spring loosen the screw at the front of the contact block then remove the contact barrel and sleeve as a complete unit Unscrew the cap E The contact and its flat spiral mounting spring may then be removed See Figure 6 The moving contact may be removed by loosening the screw that se...

Page 13: ...ll be necessary to readjust the core The core is adjusted by loosening the core locknut and rotating the core slightly to the right or left to return the moving contact arm to its floating position The core locknut is located in the center of the lower iron casting The core is turned by putting an offset screwdriver into the jewel screw slot The locknut shou1d only be 1oosened enough to a11ow the ...

Page 14: ...y watching the hairpin clip at the top of the moving contact shaft If the hairpin clip is not turning then the clutch is not slipping If the clutch slips at 10 amperes then the clutch should be tightened This is done by loosening the locknut on the right side of the moving contact assembly and then turning the adjusting screw in until the clutch stops slipping The locknut should then be retightene...

Page 15: ...radle Blocks Type CCP13E Relay Internal Connections Barrel Type Contact Assembly Phase Angle Characteristics of Type CCP13E Relay when Set for 0 004 Amp pickup at Rated Voltage and Maximum Torque Angle Type CCP13E Relay Removed from Case Front View Type CCP13E Relay Removed from Case Back View Connections for checking the polarity of Type CCP13E Relay Test Connections for Checking Pickup and Clutc...

Page 16: ...K 65525 CCP I C I SOURCE I TRANSF r I LOAD SYSTEM CCP f 2 TRANSF 2 J I SOURCE 1 2 C F Figure 1 0285A9917 Classical Application of Type CCP13E Relay 16 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 17: ... 1T7A TIME L Z y REIAY______ Clf CUIT S2 BHEAKER 2 3 NOTE i P011 PHASE SEGLJENCE OPPOSITE TO THAT INDICATE D IiHERCHt C F CONNECTIONS BETWEEN B R IN BOTH THE POTENTIAL 8 CVRRfNT CIRCUITS NOTE 2 THE 52 a SWITCH IS PROVIDED TO BREAK UP A POSSIBLE SNEAK CIRCUIT AS AN ALTERNATIVE USE A DIODE IN THE LOCATION SHOWN Figure 2 0275A4413 4 Typical External Connections for Type CCP13E Relay Revised since las...

Page 18: ... I I J _I_ I 218_j 5MM PANEL DRILLING FOR SEMI FLUSH MOUNTING FRONT VIEW TYPICAL DIM 3 0 76MM 5 25 133MM 3 4 DRILL 20 HOLES 19MM 9 7 5 3 1 00000 00000 10 8 6 4 2 BACK VIE J CUTOUT MAY REPLACE HOLE PANEL DRILLING FOR SURFACE MOUNTING FRONT VIEW 5 16 18 STUD INCHES MM VIE J SHO JING ASSEMBLY OF HARDWARE FOR SURFACE MTG ON STEEL PANELS Figure 3 K6209274 6 Outline and Panel Drilling Dimensions Diagram...

Page 19: ..._ 0 n A VI CONNECTING PLUG MA IN BRUSH AUXILIARY BRUSH CONNECTING BLOCK TERMINAL BLOCK SHORTING BAR NOTE AFTER ENGAGING AUXILIARY BRUSH CONNECTING PLUG TRAVELS Y4 INCH BEFORE ENGAG ING THE MAIN BRUSH ON THE TERMINAL BLOCK en 1 1 1 I en 1 1 1 1 1 1 N 1 1 1 E l e c t r i c a l P a r t M a n u a l s c ...

Page 20: ...65525 15 17 14 A I I f8 li r R SISTORS o TO t mou COTTOM L r 1 U NI T U J I T UN IT r v 9 l 2 4 6 8 SHORT FINGER SI Figure 5 0275A4384 Type CCP13E Relay Internal Connections 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 21: ...TUBE GEK 65525 D SPACER E CAP C D E B STA I N LESS STEEL BALL C D APHRAM F FLAT 5P RAL SPRING G CONTACT Figure 6 6077069 4 Barrel Type Contact Assembly 21 F G w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 22: ...25 30 0 330 Figure 7 K6556481 1 Phase Angle Characteristics of Type CCP13E Relay when Set for 0 004 Amp pickup at Rated Voltage and Maximum Torque Angle 22 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 23: ... GEK 65525 TARGET BARREL TYPE CONTACT ASSEMBLY TOP UNIT MIDDLE UNIT BOTTOM UNIT Figure 8 8043506 Type CCP13E Relay Removed from Case Front View 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 24: ...GEK 65525 Figure 9 8043507 Type CCP13E Relay Removed from Case Back View 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 25: ...NIT RES 50 100 OHMS RES MIDDLE UNIT RATED VOLTAGE NOTE LEFT HAND CONTACT FRONT VIEW SHOULD CLOSE RATED VOLTAGE Figure 10 6507918 Connections for checking the polarity of Type CCP13E Relay 25 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 26: ...OLTAGE AND FREQUENCY 3 8 13 14 15 16 17 18 L MA ___j LOAD BOX Figure 11 0104A8511 Test Connections for Checking Pickup and Clutch Adjustments of Type CCP13E Relay 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 27: ...N PHASE ANGLE METER WHIOi READS THE ANGLE BY WHIOi I LEADS E POWER CONNECTIONS POTENTIAL CURRENT STUDS A 8 STUDS C D 13 14 3 4 15 16 5 6 17 18 7 8 A 8 R POTENTIAL CIRCUIT Figure 12 0104A8512 Test Connections for Making the Torque Adjustments of the Type CCP13E Relay 27 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 28: ...z X TO K Y TO N TO TO TO TO 0 75 30 345 300 M TO H P TO L f u 120 t 75 T 300 t 345 t w R TO G S TO C z z X TO L Y TO P TO TO TO TO 0 75 30 345 300 u M TO H N TO K 3 R TO D S TO A 120 t 750t 300 t 345 t w X TO H Y TO M TO TO O TO TO Cl N TO K P TO L 75 30 345 300 t THESE RANGES Or PHASE ANGLE METER READINGS ARE THE ANGLES BY WHICH THE CURRENT LEADS THE VOLTAGE WITH THE DESCRIBED CONDITIONS OF LOAD ...

Page 29: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 30: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 31: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 32: ... 91 200 Meter and Control Business Department General Electric Company Protection and Control 205 Great Valley Parkway Malvern Pennsylvania 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Reviews: