GEK-65525 

A  cutaway  view  of  the  case,  cradle  blocks,  and  connection  plug  is  shown  in  Figure  4. 

DRAWOUT  RELAYS,  GENERAL 

Since  all  drawout  relays  in  service  operate  in  their  cases,  it  is  recof!lmended  that 

they  be  tested  in  their  cases  or  an  equivalent  steel  �ase. 

In.  th1s  w�y,  any 

magnetic  effects  of  the  enclosure  will  be  accurately  dupl1cated  dunng  test1ng. 

relay  may  be  tested  without  removing  it  from  the  panel,  by  using  a  12X�A13A  test 
plug. 

This  plug  makes  connections  only  with  the  relay  and  does  not  d1sturb  a�y 

shorting  bars  in  the  case. 

The  12XLA12A  test  plug  may  also  be  used;  although  th1s 

test  plug  allows  -greater  testing  flexibility,  it  requires  CT  shorting  jumpers  and 
the  exercise  of  greater  care,  since  connections  are  made  to  both  the  relay  and  the 

external  circuitry. 

POWER  REQUIREMENTS,  GENERAL 

All  alternating-current  (AC)-operated  devices  are  affected  by  frequency.  Since 

non-sinusoidal  waveforms  can  be  analyzed  as  a  fundamental  frequency  plus  harmonics 
of  the  fundamental  frequency,  it  follows  that  alternating-current  devices  (relays) 
will  be  affected  by  the  applied  waveform. 

Therefore,  in  order  to  test  alternating-current  relays  properly  it  is  essential 

to  use  a  sine  wave  of  current  and/or  voltage. 

The  purity  of  the  sine  wave  (i.e., 

its  freedom  from  harmonics)  cannot  be  expressed  as  a  finite  number  for  any 

particular  relay;  however,  any  relay  using  tuned  circuits,  RL  or  RC  networks,  or 
saturating  electromagnets  (such  as  time-overcurrent  relays),  would  be  essentially 

affected  by  non-sinusoidal  waveforms. 

DIRECTIONAL  UNITS 

Polarity 

Complete  polarity  tests  are  made  at  the  factory,  but  these  may  be  checked  by  using 

the  connections  shown  in  Figure  10.  Each  unt  should  be  checked  separately. 

The  cup 

should  rotate  in  the  direction  to  close  the  left-hand  contact  (front  view). 

Pickup 

The  pickup  of  the  CCP13E  relay  may  be  checked  by  applying  rated  voltage  and 
frequency  to  the  relay  as  in  Figure  11.  The  relay  should  close  its  left  contact  at 
the  current  specified  on  the  nameplate  (relays  are  shipped  with  current  pickup  set 
to  the  minimum  setting)  multiplied  by  1.15. 

The  1.15  multiplier  is  used  to 

compensate  for  the  test  being  made  300  off  the  angle  of  maximum  torque  (1/cos  300 

1/0.866 

1.15).  A  phase  shifter  and  phase  angle  meter  could  be  used  to  give  a  test 

circuit  that  would  test  the  units  at  the  angle  of  maximum  torque. 

However,  most 

phase-angle  meters  will  not  operate  correctly  with  only  0.004  amperes  in  their 
current  coils.  For  this  reason,  the  three-phase  test  circuit  with  phase  shifter  and 

phase-angle  meter  is 

not 

recommended. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for CCP13E

Page 1: ...INSTRUCTIONS THREE PHASE POWER DIRECTIONAL RELAY TYPE CCP13E GEK 655258 GE Meter and Control 205 Great Valley Parkway Malvern PA 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ...UNIT INSTALLATION PICKUP HIGH SEISMIC TARGET AND SEAL IN UNIT PERIODIC CHECKS AND ROUTINE MAINTENANCE PICKUP HIGH SEISMIC TARGET AND SEAL IN UNIT SERVICING RELAY CONTACTS BEARINGS V0LTAGE BIAS POLARITY ANGLE OF MAXIMUM TORQUE PICKUP ADJUSTMENT CLUTCH ADJUSTMENT HIGH SEISMIC TARGET AND SEAL IN UNIT RENEWAL PARTS LIST OF ILLUSTRATIONS PAGE 3 3 4 5 6 6 7 7 8 8 8 9 9 9 10 10 11 11 11 11 11 11 11 12 13...

Page 3: ...re 1 with normal load flow from the system to the load If a single phase to ground fault were to occur at F it would be cleared at source 2 but not necessarily at breaker 2 because of delta wye transformer 2 However it is desirable to open circuit breaker 2 to clear the ground fault completely This can be accomplished by the CCP13E relay associated with circuit breaker 2 The CCP13E is generally se...

Page 4: ...e applied voltage Thus the minimum pickup in this case will be the nameplate value divided by 0 95 and the 0 004 ampere relay will have a minimum pickup at 95 voltage of 0 004 0 95 0 0042 Secondary Amperes Based on the maximum full load current the smallest CT ratio that could be used is 500 5 With this ratio the core loss component of current would be 0 i 7 o oo567 s d A econ ary mperes Since the...

Page 5: ...ws holds the connecting plugs in place The relay case is suitable for either semiflush or to two inches thick and appropriate hardware thickness must be indicated on the relay order to be included surface mounting on all panels up is available However panel insure that proper hardware will These relays are induction cylinder devices for alternating current AC circuits The principle by which torque...

Page 6: ...ertz relay is available with potential coils rated for 115 or 208 volts The current coils of all models are rated 5 amperes continuously or 200 amperes for 1 second The relay has maximum torque when the three phase system is a unit power factor if the relay is connected as shown in Figure 2 The balanced three phase current to operate the relay at maximum torque angle and with rated voltage on the ...

Page 7: ...s studs 3 4 and Phase 1 3 on its potential coils studs 13 14 The relay will therefore respond to the watt component of the power Figure 7 The High Seismic target and seal in unit has two tap selections located on the front of the unit See Figure 8 RECEIVING HANDLING AND STORAGE These relays when not included as part of a control panel will be shipped in cartons designed to protect them against dam...

Page 8: ...cal end play of the moving contact and shaft assembly It should be between 1 64 inch and 1 32 inch 6 The contact gap should be approximately 3 64 inch 7 The contact wipe should be 0 004 inch to 0 009 inch If there is reason to believe that the jewel is cracked or dirty the screw assembly can be removed from the bottom of the unit and examined under a microscope or the surface of the jewel explored...

Page 9: ...and or voltage The purity of the sine wave i e its freedom from harmonics cannot be expressed as a finite number for any particular relay however any relay using tuned circuits RL or RC networks or saturating electromagnets such as time overcurrent relays would be essentially affected by non sinusoidal waveforms DIRECTIONAL UNITS Polarity Complete polarity tests are made at the factory but these m...

Page 10: ...inals 1 and 11 to a DC source using a load box to control the current over a range of 0 1 to 2 amperes 2 Close the left contact manually 3 Increase the current slowly until the seal in unit picks up See Table IV The target must latch in 4 Decrease the current slowly until the seal in unit drops out See Table IV The target must remain latched in Reset the target before checking pickup again TAP 0 2...

Page 11: ...rience to select the test interval best suited to his individual requirements it is suggested that the points listed under ACCEPTANCE TESTS be checked at an interval of from one to two years These tests are intended to make sure that the relays have not deviated from their original settings If deviations are encountered the relay must be retested and serviced as described in this manual PICKUP Per...

Page 12: ... left hand contact barrel 1 revolutions 5400 and tighten its clamping screw To change the stationary contact mounting spring loosen the screw at the front of the contact block then remove the contact barrel and sleeve as a complete unit Unscrew the cap E The contact and its flat spiral mounting spring may then be removed See Figure 6 The moving contact may be removed by loosening the screw that se...

Page 13: ...ll be necessary to readjust the core The core is adjusted by loosening the core locknut and rotating the core slightly to the right or left to return the moving contact arm to its floating position The core locknut is located in the center of the lower iron casting The core is turned by putting an offset screwdriver into the jewel screw slot The locknut shou1d only be 1oosened enough to a11ow the ...

Page 14: ...y watching the hairpin clip at the top of the moving contact shaft If the hairpin clip is not turning then the clutch is not slipping If the clutch slips at 10 amperes then the clutch should be tightened This is done by loosening the locknut on the right side of the moving contact assembly and then turning the adjusting screw in until the clutch stops slipping The locknut should then be retightene...

Page 15: ...radle Blocks Type CCP13E Relay Internal Connections Barrel Type Contact Assembly Phase Angle Characteristics of Type CCP13E Relay when Set for 0 004 Amp pickup at Rated Voltage and Maximum Torque Angle Type CCP13E Relay Removed from Case Front View Type CCP13E Relay Removed from Case Back View Connections for checking the polarity of Type CCP13E Relay Test Connections for Checking Pickup and Clutc...

Page 16: ...K 65525 CCP I C I SOURCE I TRANSF r I LOAD SYSTEM CCP f 2 TRANSF 2 J I SOURCE 1 2 C F Figure 1 0285A9917 Classical Application of Type CCP13E Relay 16 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 17: ... 1T7A TIME L Z y REIAY______ Clf CUIT S2 BHEAKER 2 3 NOTE i P011 PHASE SEGLJENCE OPPOSITE TO THAT INDICATE D IiHERCHt C F CONNECTIONS BETWEEN B R IN BOTH THE POTENTIAL 8 CVRRfNT CIRCUITS NOTE 2 THE 52 a SWITCH IS PROVIDED TO BREAK UP A POSSIBLE SNEAK CIRCUIT AS AN ALTERNATIVE USE A DIODE IN THE LOCATION SHOWN Figure 2 0275A4413 4 Typical External Connections for Type CCP13E Relay Revised since las...

Page 18: ... I I J _I_ I 218_j 5MM PANEL DRILLING FOR SEMI FLUSH MOUNTING FRONT VIEW TYPICAL DIM 3 0 76MM 5 25 133MM 3 4 DRILL 20 HOLES 19MM 9 7 5 3 1 00000 00000 10 8 6 4 2 BACK VIE J CUTOUT MAY REPLACE HOLE PANEL DRILLING FOR SURFACE MOUNTING FRONT VIEW 5 16 18 STUD INCHES MM VIE J SHO JING ASSEMBLY OF HARDWARE FOR SURFACE MTG ON STEEL PANELS Figure 3 K6209274 6 Outline and Panel Drilling Dimensions Diagram...

Page 19: ..._ 0 n A VI CONNECTING PLUG MA IN BRUSH AUXILIARY BRUSH CONNECTING BLOCK TERMINAL BLOCK SHORTING BAR NOTE AFTER ENGAGING AUXILIARY BRUSH CONNECTING PLUG TRAVELS Y4 INCH BEFORE ENGAG ING THE MAIN BRUSH ON THE TERMINAL BLOCK en 1 1 1 I en 1 1 1 1 1 1 N 1 1 1 E l e c t r i c a l P a r t M a n u a l s c ...

Page 20: ...65525 15 17 14 A I I f8 li r R SISTORS o TO t mou COTTOM L r 1 U NI T U J I T UN IT r v 9 l 2 4 6 8 SHORT FINGER SI Figure 5 0275A4384 Type CCP13E Relay Internal Connections 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 21: ...TUBE GEK 65525 D SPACER E CAP C D E B STA I N LESS STEEL BALL C D APHRAM F FLAT 5P RAL SPRING G CONTACT Figure 6 6077069 4 Barrel Type Contact Assembly 21 F G w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 22: ...25 30 0 330 Figure 7 K6556481 1 Phase Angle Characteristics of Type CCP13E Relay when Set for 0 004 Amp pickup at Rated Voltage and Maximum Torque Angle 22 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 23: ... GEK 65525 TARGET BARREL TYPE CONTACT ASSEMBLY TOP UNIT MIDDLE UNIT BOTTOM UNIT Figure 8 8043506 Type CCP13E Relay Removed from Case Front View 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 24: ...GEK 65525 Figure 9 8043507 Type CCP13E Relay Removed from Case Back View 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 25: ...NIT RES 50 100 OHMS RES MIDDLE UNIT RATED VOLTAGE NOTE LEFT HAND CONTACT FRONT VIEW SHOULD CLOSE RATED VOLTAGE Figure 10 6507918 Connections for checking the polarity of Type CCP13E Relay 25 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 26: ...OLTAGE AND FREQUENCY 3 8 13 14 15 16 17 18 L MA ___j LOAD BOX Figure 11 0104A8511 Test Connections for Checking Pickup and Clutch Adjustments of Type CCP13E Relay 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 27: ...N PHASE ANGLE METER WHIOi READS THE ANGLE BY WHIOi I LEADS E POWER CONNECTIONS POTENTIAL CURRENT STUDS A 8 STUDS C D 13 14 3 4 15 16 5 6 17 18 7 8 A 8 R POTENTIAL CIRCUIT Figure 12 0104A8512 Test Connections for Making the Torque Adjustments of the Type CCP13E Relay 27 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 28: ...z X TO K Y TO N TO TO TO TO 0 75 30 345 300 M TO H P TO L f u 120 t 75 T 300 t 345 t w R TO G S TO C z z X TO L Y TO P TO TO TO TO 0 75 30 345 300 u M TO H N TO K 3 R TO D S TO A 120 t 750t 300 t 345 t w X TO H Y TO M TO TO O TO TO Cl N TO K P TO L 75 30 345 300 t THESE RANGES Or PHASE ANGLE METER READINGS ARE THE ANGLES BY WHICH THE CURRENT LEADS THE VOLTAGE WITH THE DESCRIBED CONDITIONS OF LOAD ...

Page 29: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 30: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 31: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 32: ... 91 200 Meter and Control Business Department General Electric Company Protection and Control 205 Great Valley Parkway Malvern Pennsylvania 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Reviews: