3-58
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
SET UP CYBERSENTRY AND CHANGE DEFAULT PASSWORD
CHAPTER 3: INSTALLATION
3
Figure 3-59: Quick Connect window to access a device
5.
Select the serial
Interface
and the communications port (
COM Port
) from the drop-down lists, then click
Connect
. The
COM Port is that of the computer.
6.
The EnerVista software creates a site named “Quick Connect” with a corresponding device also named “Quick
Connect” and displays them in the Online Window. Expand the sections to view data directly from the UR device. Use
the
Device Setup
button to change the site name.
Each time that the EnerVista UR Setup software is initialized, click the
Quick Connect
button to establish direct
communications to the C30. This ensures that configuration of the EnerVista UR Setup software matches the C30 model
number.
3.8.3 Use Quick Connect via a rear Ethernet port
To connect to a UR using an Ethernet cable:
1.
In the EnerVista software, click the
Quick Connect
button. The window opens.
2.
Select the
Ethernet
interface and enter the IP address assigned to the C30, then click the
Connect
button. The
EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named "Quick
Connect" and displays them in the Online Window.
3.
Expand the sections to view data directly from the C30 device. Use the
Device Setup
button to change the site name.
Each time that the EnerVista software is initialized, click the
Quick Connect
button to establish direct communications to
the C30. This ensures that configuration of the EnerVista UR Setup software matches the C30 model number.
3.9 Set up CyberSentry and change default password
If and when first using CyberSentry security, use the following procedure for set up.
1.
Log in to the relay as Administrator by using the
VALUE
keys on the front panel or through EnerVista connected serially
(so that no IP address is required). If logging in through EnerVista choose Device authentication. Enter the default