2-24
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
2
CONTROL POWER EXTERNAL OUTPUT (FOR DRY CONTACT INPUT)
Capacity:
100 mA DC at 48 V DC
Isolation:
±300 Vpk
DIRECT OUTPUTS
Output points:
64
DCMA OUTPUTS
Range:
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance:
12 k
Ω
for –1 to 1 mA range
12 k
Ω
for 0 to 1 mA range
600
Ω
for 4 to 20 mA range
Accuracy:
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change:
100 ms
Isolation:
1.5 kV
Driving signal:
any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of 0.001
2.5.7 Communication protocols
IEC 61850
IEC 61850:
Supports IEC 61850 Edition 2.0. See the UR Family Communications Guide and its conformance
statements.
RS232
Front port:
19.2 or 115.2 kbps, Modbus RTU
RS485
1 rear port:
up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103
Typical distance:
1200 m
Isolation:
2 kV, isolated together at 36 Vpk
FIBER ETHERNET PORT
ETHERNET (10/100 MB TWISTED PAIR)
Modes:
10 Mb, 10/100 Mb (auto-detect)
Connector:
RJ45
SIMPLE NETWORK TIME PROTOCOL (SNTP)
Clock synchronization error:
<10 ms (typical)
Parameter
Fiber type
100 Mb multimode
Wavelength
1310 nm
Connector
LC
Transmit power
–20 dBm
Receiver sensitivity
–30 dBm
Power budget
10 dB
Maximum input power
–14 dBm
Typical distance
2 km
Full duplex
yes
Redundancy
yes